Mitsubishi Electric PUHZ-HRP71VHA Service Manual page 75

Split-type, heat pump air conditioners
Hide thumbs Also See for PUHZ-HRP71VHA:
Table of Contents

Advertisement

Outdoor power circuit board
PUHZ-HRP100YHA
PUHZ-HRP100YHA2
PUHZ-HRP100YHA2R1
PUHZ-HRP125YHA
PUHZ-HRP125YHA2
PUHZ-HRP125YHA2R1
CN5
CN4
Detection of
Connect to the
primary current
outdoor controller
(Connect to the
circuit board
outdoor noise filter
(CN4)
circuit board (CNCT))
TAB connecter
on X52A
Connect to the
RS resistor
Connect to DCL
OCH425F
Brief Check of POWER MODULE
* Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.).
If they are short-circuited, it means that they are broken.
1. Check of POWER MODULE
1.Check of DIODE circuit
L1 - P1 , L2 - P1 , L3 - P1 , L1 - N1 , L2 - N1 , L3 - N1
2.Check of IGBT circuit
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
Note:The marks, L1 , L2 , L3 , N1 , N2 , P1 , P2 , U , V and W
shown in the diagram are not actually printed on the board.
CN7
Connect to the
outdoor converter
circuit board
(CN7)
P1
P2
TB-P2
Connect to the smoothing
+
capacitor CB1
75
CN2
Connect to the outdoor controller circuit
board (CN2)
1-5: Power circuit board
signal to the controller board (0-5V DC)
2-5: Zero cross signal (0-5V DC)
3-4: Not used [ 5 : –
6-5: 16V DC
7-5: 16V DC
W
V
W
U
W
L3
L2
L1
N1
N2
TB-C1
POWER
Connect to the
MODULE
smoothing capacitor
+
CB1
, CB2
Transmitting
1, 2, 6, 7 : + ]
TB-U, TB-V,
TB-W
Connect to the
compressor (MC)
Voltage among
phases:
10V-400V AC
TB-L1, TB-L2, TB-L3
Connect to the
outdoor noise filter
circuit board
(L1-L01, L2-L02,
L3-L03)
380V-415V AC
TB-N1
Connect to the
smoothing capacitor
CB2