Self-Diagnosis Action Table - Mitsubishi Electric PUHZ-HRP71VHA Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUHZ-HRP71VHA:
Table of Contents

Advertisement

11-4. SELF-DIAGNOSIS ACTION TABLE

<Abnormalities detected when the power is turned on>
Abnormal point and detection method
Error Code
None
63L connector open
Abnormal if 63L connector circuit is open for
3 minutes continuously after power supply.
63L: Low-pressure switch
F3
(5202)
63H connector open
Abnormal if 63H connector circuit is open for
3 minutes continuously after power supply.
63H: High-pressure switch
F5
(5201)
OCH425F
1 No voltage is supplied to terminal
block (TB1) of outdoor unit.
a) Power supply breaker is
turned off.
b) Contact failure or
disconnection of power
supply terminal
c) Open phase (L or N phase)
2 Electric power is not charged
to power supply terminal of
outdoor power circuit board.
a) Contact failure of power
supply terminal
b) Open phase on the outdoor
power circuit board
HRP71, 100VHA :
Disconnection of connector
TABT or TABS
HRP71, 100VHA2 :
Disconnection of connector
LI or NI
3 Electric power is not supplied
to outdoor controller circuit
board.
a) Disconnection of connector
(CNDC)
4 Disconnection of reactor (DCL
or ACL)
5 Disconnection of outdoor noise
filter circuit board or parts failure
in outdoor noise filter circuit
board
As for HRP71, 100VHA, it is
especially needed to check the
resistance RS1 on the noise
filter circuit board.
6 Defective outdoor power circuit
board
7 Defective outdoor controller
circuit board
1 Disconnection or contact failure
of 63L connector on outdoor
controller circuit board
2 Disconnection or contact failure
of 63L
3 63L is working due to
refrigerant leakage or defective
parts.
4 Defective outdoor controller
circuit board
1 Disconnection or contact failure
of 63H connector on outdoor
controller circuit board
2 Disconnection or contact failure
of 63H
3 63H is working due to defective
parts.
4 Defective outdoor controller
circuit board
(Note 1) Refer to indoor unit section for code P and code E.
Case
1 Check following items.
a) Power supply breaker
b) Connection of power supply terminal block
(TB1)
c) Connection of power supply terminal block
(TB1)
2 Check following items.
a) Connection of power supply terminal block
(TB1)
b) Connection of terminal on outdoor power
circuit board
HRP71, 100VHA : Check connection of
HRP71, 100VHA2 : Check connection of
3 Check connection of the connector (CNDC)
on the outdoor controller circuit board.
Check connection of the connector, CNDC on
the outdoor power circuit board(V)/the noise
filter(Y). Refer to 11-9.
4 Check connection of reactor. (DCL or ACL)
HRP71, 100VHA : Check connection of "L1"
HRP71, 100VHA2 : Check connection of
5 a) Check connection of outdoor noise filter
circuit board.
b) Replace outdoor noise filter circuit board.
Refer to 11-9.
6 Replace outdoor power circuit board.
7 Replace controller board (When items above
are checked but the units can not be repaired).
1 Check connection of 63L connector on
outdoor controller circuit board.
Refer to 11-9.
2 Check the 63L side of connecting wire.
3 Check refrigerant pressure.
Charge additional refrigerant.
Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller circuit board.
1 Check connection of 63H connector on
outdoor controller circuit board.
Refer to 11-9.
2 Check the 63H side of connecting wire.
3 Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller circuit board.
40
Judgment and action
the connector TABT or
TABS. Refer to 11-9.
the connector LI or NI.
Refer to 11-9.
and "L2" on the active filter
module.(ACTM)
Refer to 11-9.
"DCL1" and "DCL2" on
the outdoor power circuit
board. Refer to 11-9.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents