Bryant 582A Installation, Start-Up, And Operating Instructions Manual page 4

Single packaged gas heating/ electric cooling units
Table of Contents

Advertisement

REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
TOP OF UNIT...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT .............................................................................0.50 [12.7]
FLUE PANEL ....................................................................................36.00 [914.4]
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
UNIT
ELECTRICAL CHARACTERISTICS
582A048090/115/130
208-230/1/60, 208/230-3-60, 460-3-60
582A060090/115/130
208/230-1-60, 208/230-3-60, 460-3-60
583A042060/090
208/230-1-60, 208/230-3-60, 460-3-60
583A048090/115/130
208/230-1-60, 208/230-3-60, 460-3-60
583A060090/115/130
208/230-1-60, 208/230-3-60, 460-3-60
INCHES [mm]
INCHES [mm]
UNIT WEIGHT
lb
415
450
382
421
468
Fig. 3—582A048-060 and 583A042-060 Unit Dimensions
—4—
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]
POWER ENTRY SIDE....................................................................36.00 [914.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]
DUCT PANEL .................................................................................12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
UNIT HEIGHT IN. (MM)
"A"
kg
188.6
38.98 (990.2)
204.5
38.98 (990.2)
173.3
38.98 (990.2)
191.0
38.98 (990.2)
212.3
42.98 (1091.1)
INCHES [mm]
LEGEND
CG - Center of Gravity
COND - Condensor
EVAP - Evaporator
NEC - National Electrical Code
REQ'D - Required
NOTE: Dimensions are in in. [mm]
CENTER OF GRAVITY
IN. (MM)
X
Y
22 (558.5)
16 (406.4)
17 (432.0)
22 (558.5)
16 (406.4)
17 (432.0)
23.0 (584.2)
16.3 (412.8)
16.6 (421.6)
21.5 (546.1)
16.6 (422.1)
18.0 (457.2)
23.5 (596.9)
16.3 (412.8)
17.6 (447.0)
C00056