TABLE 13—DRY COIL AIR DELIVERY* – HORIZONTAL AND DOWNFLOW DISCHARGE –
Motor
Unit
Speed
Watts
Low
Cfm
Watts
024
Med
Cfm
Watts
High
Cfm
Watts
Low
Cfm
Watts
030
Med
Cfm
Watts
High
Cfm
Watts
Low
Cfm
Watts
036
Med
Cfm
Watts
High
Cfm
Watts
Low
Cfm
Watts
042
Med
Cfm
Watts
High
Cfm
Watts
Low
Cfm
Watts
048
Med
Cfm
Watts
High
Cfm
Watts
Low
Cfm
Watts
060
Med
Cfm
Watts
High
Cfm
* Air delivery values are without air filter and are for dry coil (See Table 15–583A Wet Coil Pressure Drop table).
NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
WARNING: The ability to properly perform mainte-
nance on this equipment requires certain expertise, me-
chanical skills, tools, and equipment. If you do not
possess these, do not attempt to perform any maintenance
on this equipment other than those procedures recom-
mended in the User's Manual. FAILURE TO HEED
THIS WARNING COULD RESULT IN SERIOUS IN-
JURY AND POSSIBLE DAMAGE TO THIS EQUIP-
MENT.
UNIT 583A024-060 (DEDUCT 10 PERCENT FOR 208 VOLTS)
230 AND 460 VOLT
0.0
0.1
0.2
281
282
281
899
828
757
—
—
—
—
—
—
—
—
—
—
—
—
246
244
243
982
860
808
343
339
336
1233
1170
1109
—
—
—
—
—
—
—
470
458
—
1463
1406
—
—
514
—
—
1497
—
—
—
—
—
—
643
625
614
1626
1614
1579
—
—
—
—
—
—
—
—
—
—
—
—
614
588
577
1591
1549
1518
778
756
738
1854
1837
1804
—
—
—
—
—
—
834
813
782
2016
1955
1898
941
889
851
2379
2233
2124
—
—
960
—
—
2497
External Static Pressure (in. wg)
0.3
0.4
0.5
278
276
—
691
619
—
375
370
363
969
897
824
—
—
468
—
—
994
241
—
—
736
—
—
332
328
322
1038
953
855
—
441
432
—
1202
1111
445
430
415
1344
1273
1188
501
487
471
1428
1348
1255
646
636
626
1491
1412
1325
605
593
574
1532
1478
1421
—
726
695
—
1731
1672
—
—
—
—
—
—
572
566
556
1490
1460
1421
719
699
676
1759
1705
1643
—
896
862
—
1956
1879
746
712
680
1840
1781
1717
822
797
772
2038
1964
1892
949
920
883
2224
2075
1986
WARNING: Failure to follow these warnings could
result in serious injury:
1. First, turn off gas supply to the unit. Then turn off
electrical power to the unit and install lockout tag
before performing any maintenance or service on the
unit.
2. Use extreme caution when removing panels and parts.
As with any mechanical equipment, personal injury
can result from sharp edges, etc.
3. Never place anything combustible either on, or in
contact with, the unit.
4. Should overheating occur or the gas supply fail to shut
off, turn off external main manual gas valve to the unit.
Then shut off electrical supply and install lockout tag.
—23—
0.6
0.7
0.8
—
—
—
—
—
—
357
352
—
744
649
—
457
444
431
913
826
730
—
—
—
—
—
—
317
—
—
754
—
—
421
410
400
1021
929
826
399
384
—
1091
983
—
455
438
422
1152
1042
929
614
602
589
1228
1120
1003
549
518
485
1361
1295
1218
661
625
591
1610
1541
1456
—
790
766
—
1699
1602
539
517
491
1372
1312
1242
650
623
596
1577
1508
1440
829
800
775
1797
1709
1615
652
626
—
1646
1566
—
745
714
679
1814
1727
1626
845
812
783
1915
1831
1721
0.9
1.0
—
—
—
—
—
—
—
—
423
—
620
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
454
—
1120
—
561
540
1345
1193
742
713
1494
1367
—
—
—
—
572
555
1375
1315
752
728
1514
1406
—
—
—
—
639
—
1511
—
753
—
1588
—