Bryant 582A Installation, Start-Up, And Operating Instructions Manual page 16

Single packaged gas heating/ electric cooling units
Table of Contents

Advertisement

FIELD
SUPPLY
EQUIP_GND
POWER
SCHEMATIC
208/230-1-60
COOLING FAN LOGIC
0
T
T+30
G
G
ENERGIZED
DE-ENERGIZED
HEATING FAN LOGIC
0
45
T
T+30
W
BR
W
BR
ENERGIZED
DE-ENERGIZED
RC
24V SPLICE BOX
RH
OFF
HEAT
B
AUTO
COOL
AHA
THI
WI
OFF
HEAT
AUTO
TCI
YI
COOL
AUTO
G
FAN
SW
ON
FIELD-THERMOSTAT
COMMON
UNIT COMPONENT ARRANGEMENT
OUTDOOR FAN
OFM
SECTION
COMPRESSOR
CONTROL BOX
INDOOR FAN
SECTION
LS1
SECTION
23
TRAN
21
CAP 1
CAP3
IGC
IFM
CAP 2
HC
F
24V
SPLICE BOX
COMP
IDM
HS
LS2
MGV
C
1 2
S
R
1
FS
CAP 1
LARGE CHASSIS LOC
GAS SECTION
Fig. 15—208/230-1-60 Wiring Diagram, Units 582A and 583A
C
W6 YEL
11
21
1
23
13
1
ST
(582A ONLY)
(SEE NOTE #4)
W16 YEL
W15 YEL
PRIMARY
230V
W14 BLK
230
COM
200
TRAN1
SECONDARY
24V
24V
C
CR
W13 BLK
L1
BR
W39 RED
J2
IGC
IFC
W19 WHT
W
W20 GRN
G
R
W21 RED
RS
CR
RS
LS
FAN
LS
BR
LOGIC
CS
CS
SAFETY
GVR
LOGIC
GV
GV
HV
TRAN
1 2 3
HS
AHA
– Adjustable Heat
Anticipator
EQUIP
GND
BR
– Blower Relay
C
– Contactor
CAP
– Capacitor
13
COMP – Compressor Motor
C
CR
– Combustion Relay
11
CS
– Centrifugal Switch
EQUIP – Equipment
FS
– Flame Sensor
FU
– Fuse
GND
– Ground
GV
– Gas Valve
GVR
– Gas Valve Relay
HS
– Hall Effect Sensor
HV
– High Voltage
TRAN – Transformer
I
– Ignitor
IDM
– Induced-Draft Motor
IFC
– Indoor-Fan Contactor
IFM
– Indoor-Fan Motor
IGC
– Integrated Gas Unit
Controller
L1
– Line
RS
LS
– Limit Switch
LS1
– Limit Switch
MGV
– Main Gas Valve
NOTES:
1. If any of the original wires furnished are replaced, they must be
replaced with type 90 degree C wire or its equivalent.
2. See price pages for thermostat and subbases.
3. Use 75 degree C copper conductors for field installation.
4. For high speed IFM, disconnect RED wire from IGC terminal BM
and connect BLK wire from IFM. For medium speed, disconnect
RED wire from IGC terminal BM and connect BLU wire from IFM.
5. Models 4BGX024-036 have LS1 and LS2 wired in series. Models
48GX042-060 have LS1 only.
—16—
W43 BLK
BLK
YEL
W61 YEL
CAP 2
BRN
H
F
C
W8 BLK
YEL
C
W7 YEL
R
W59 BLU
W9 BLU
S
RED
YEL
BRN/WHT
OR YEL
CAP 1
BRN
QT
V10
YEL
CAP 3
BRN
QT
GRN-YEL
CM
BM
L2
L2
L2
5 AMP
FU
RT
BLU
RS
BLU
1
3
V10
LS1
LS2
V10
V10
1
3
1
MGV
GVR
YEL
W35 GRA
1
W34 BRN
FLAME SEN
YEL
FS
BRN
W41 GRN-YEL
C
W32 BRN
C
W46 BRN
C1
C_
GROUNDED
TRU STANDOFF
W33 YEL
DISCONNECT
PER NEC
LEGEND
NEC
– National Electrical
Code
OFM
– Outdoor-Fan Motor
QT
– Quadruple Terminal
RS
– Rollout Switch
SEN
– Sensor
SW
– Switch
TRAN – Transformer
Field Splice
Terminal (Marked)
Terminal (Unmarked)
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or
Optional Wiring
To Indicate Common
Potential Only, Not
to Represent Wiring
OFM
COMP
IFM
IDM
W46 BRN
SEE NOTE #5
3
2
GRN-YEL
C2
W32 BRN
W30 BRN
W30 BRN
C00057

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

583a

Table of Contents