UV100E ULTRAVIOLET AIR TREATMENT SYSTEM

SPECIFICATIONS

IMPORTANT
The specifications in this publication do not include-
normal manufacturing tolerances; therefore, an indi-
vidual unit may not exactly match the listed
specifications. This product is tested and calibrated
under closely controlled conditions and some minor
differences in performance can be expected if those
conditions are changed.
TRADELINE® Models available:
The UV100A Ultraviolet Air Treatment System is available in
three models: a single-lamp, moderate-efficiency return air
unit; a dual-lamp, high-efficiency return air unit; and an air
conditioner coil irradiation unit.
• UV100E single-lamp unit is mounted in the return air duct
of an HVAC system. It has moderate-efficiency
performance against airborne bacteria in return air
applications.
• UV100E dual-lamp unit is mounted in the return air duct of
an HVAC system. It has high-efficiency performance
against airborne bacteria in return air applications.
• UV100E coil irradiation unit is mounted downstream from
the air conditioner cooling coils or in the return air duct of
the HVAC system. The single-lamp unit reduces mold
growth and spores on duct surfaces, coils and drip pans.
Efficiencies:
• UV100E Coil Irradiation unit: Kills up to 99.9% of mold on
system cooling coils.
— Test perfomed in a test duct showed reduction in col-
ony-forming aspergillus niger mold spores when sur-
face was irradiated at a distance of 18 in. for three
hours in still air, using new lamps.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
68-0249-1
• UV100A Dual-Lamp unit: Kills up to 87% of airborne
bacterial passing by the system.
— Test showed single-pass kill-rate of serratia marce-
scens bacteria in a clean metal 12 in. x 25 in. duct at
an airflow rate of 2000 cfm using new lamps.
• UV100A Single-Lamp unit: Kills up to 70% of airborne
bacteria passing by the system.
— Test showed single-pass kill-rate of serratia marce-
scens bacteria in a clean metal 12 in. x 25 in. duct at
an airflow rate of 2000 cfm using new lamps.
Approvals:
Underwriters Laboratories: File no. E212213.
The health aspects associated with the use of this product
and its ability to aid in disinfection of environmental air have
not been investigated by UL.
Electrical Ratings:
Power Rating: 120 Vac, 60 Hz.
Consumption:
Model
Coil Irradiation
Single-Lamp Return
Dual-lamp Return
Temperature Ratings:
Ambient Temperature Range: 30°F to 104°F (-2°C to 40°C).
Lamp Temperature Range: 30°F to 104°F (-2°C to 40°C).
Relative Humidity:
Up to 95% rh, non-condensing.
Dimensions:
See Fig. 2.
2
Input Power
Lamp Wattage
(A)
(W)
0.85
36
0.4
18
0.7
36 each lamp