Specifications; Ordering Information - Honeywell F58G Series Product Data

Commercial duct mounted electronic air cleaner
Hide thumbs Also See for F58G Series:
Table of Contents

Advertisement

F58G,H AND F58GUV SERIES COMMERCIAL DUCT MOUNTED ELECTRONIC AIR CLEANER

SPECIFICATIONS

IMPORTANT
The specifications given in this publication do not
include normal manufacturing tolerances. There-
fore, this unit may not exactly match the listed
specifications. This product is tested and calibrated
under closely controlled conditions, and some
minor differences in performance can be expected
if those conditions are changed.
Model:
See Table 1 and Table 2.
Electrical Ratings:
Power Consumption: 36W maximum without UV lamp,
100W maximum with UV lamp.
Ionizer Voltage: 8150 V d.c.
Collector Voltage: 4075 V d.c.
Microorganic purifying rate at 2000CFM: 90%
Bacterial eliminating rate: 99%
Bacteriophage eliminating rate: 99%
H3N2 eliminating rate: (Under verification)
NOTE: Above parameters are tested and collected under
strictly controlled environment and methods
required by national standard GB/T 21551.3-
2010 or GB/T 34012-2017. If external environ-
ment changes, actual performance might have
small variance compared with parameter sheet.
Capacity, Efficiency, Pressure Drop: See Fig. 1 and Fig. 2.
Temperature Ratings:
Operating Ambient: 40°F to 122°F (4°C to 50°C).
Temperature of Airflow Through Cells: 40°F to 122°F
(4°C to 50°C).
Maximum Cell Washing Temperature: 220°F (140°C).
Storage and Shipping Ambient: -40°F to +140°F
(-40°C to +60°C).
Mounting:
Mounts into the return air duct of a forced air heating cool-
ing, or ventilating system. See Planning the Installation
section.
Weight:
Electronic Cell (each): 9-3/16 lb (4.2 kg).
Shipping Weight:
F58G: 42 lb (19.1 kg).
F58H: 26.7 lb (12.1 kg).
F58G+UV: 46 lb (20.9 kg).
Installed Weight (Cells Included):
F58G: 37 lb (16.8 kg).
F58H: 24 lb (10.9 kg).
F58G+UV: 41 lb (18.6 kg).
68-0233—03
Dimensions: See Fig. 3 and Fig. 4.
Accessories:
202614 Carbon Filter.
13643AA Ionizer Wires (quantity 5).
32350736-001 UV tube.
Repair Parts: See Parts List section.
Regulatory Approvals:
Ozone-free UV tube meets Chinese national standard of
GB19258-2012.
EPA Est. No. 98423-CHN-1
Table 1. F58 Models without UV.
Voltage /
Product Code
Frequency
F58G1014
120V 60Hz
220~240V
F58G1016
50/60Hz;
220~240V
F58G1028
50/60Hz;
120V 60Hz
F58H1006
N/A*
*Must be installed with F58G, no power supply.
Table 2. F58 Models with UV.
Voltage /
Product Code
Frequency
F58G1014UV
120V 60Hz
220~240V
F58G1016UV
50/60Hz;
220~240V
F58G1024UV
50/60Hz;
120V 60Hz
WARNING
Only qualified technicians should install this
product.
Install so that direct UV light is not visible in
occupied space.
If there is a direct line of sight from the product to
an occupied area, a minimum distance of 90 yards
(83 meters) must be maintained in order to ensure
safe UV-C exposure levels for the user.
If there is direct line of site to a service area, a
minimum distance of 22 yards (20 meters) must be
maintained unless protective equipment is used.
2
Wash
Rated Air
BMS
Light
Volume
2000 CFM
3
(3400 m
/hr)
1000 CFM
3
(1700m
/hr)
Wash
Rated Air
BMS
Light
Volume
2000 CFM
3
(3400 m
/hr)

Hide quick links:

Advertisement

Table of Contents
loading