1.9.4 Analog Input Type Codes and Data Format

Type Code
Input Type
+4 to +20
07
mA
-10 to +10
08
-5 to +5
09
-1 to +1
0A
-500 to +500
0B
mV
-150 to +150
0C
mV
-20 to +20
0D
mA
0 to +20
1A
mA
M-7026 User Manual Rev: 1.5 Date: 2016/03/10
Data Format
Engineering Units
% of FSR
2's Complement Hexadecimal
Engineering Units
% of FSR
V
2's Complement Hexadecimal
Engineering Units
% of FSR
V
2's Complement Hexadecimal
Engineering Units
% of FSR
V
2's Complement Hexadecimal
Engineering Units
% of FSR
2's Complement Hexadecimal
Engineering Units
% of FSR
2's Complement Hexadecimal
Engineering Units
% of FSR
2's Complement Hexadecimal
Engineering Units
% of FSR
2's Complement Hexadecimal
+F.S
-F.S.
+20.000
+04.000
+100.00
+000.00
FFFF
0000
+10.000
-10.000
+100.00
-100.00
7FFF
8000
+5.0000
-5.0000
+100.00
-100.00
7FFF
8000
+1.0000
-1.0000
+100.00
-100.00
7FFF
8000
+500.00
-500.00
+100.00
-100.00
7FFF
8000
+150.00
-150.00
+100.00
-100.00
7FFF
8000
+20.000
-20.000
+100.00
-100.00
7FFF
8000
+20.000
+00.000
+100.00
+000.00
FFFF
0000