SPECIFICATIONS 12.5 EGTD
AC GENERATOR (Single Phase)
AC GENERATOR (3 Phase)
Single Phase
Voltage
Voltage regulation:
Frequency regulation:
Rating (Volts AC)
60 Hertz (1800 rpm)
12.5KW
50 Hertz (1500 rpm)
9.3KW
Generator Cooling
Air Requirements
(60 Hertz) at 1800 rpm
Generator Compartment
Ambient Temperature
Recommendations
Brushless, tour-pole, revolving field.
Pre-lubricated, single bearing design.
Reconnectable, single phase transformer
regulation (optional solid-state voltage
regulation).
120 or 120/240 Volts - 60 Hertz
230 Volts - 50 Hertz
± 5% no load to full load.
.5 Hertz (.6%) no load to full load.
120 Volts
104 Amps
120/240 Volts
104/52 Amps
230 Volts
60Amps
225 - 250 cfm (5.66- 6.37 cmm)
NOTE:
Increase air supply 15% for 50 Hertz
operation (1500 rpm)
122oF (50°G) maximum
NOTE:
Forced ventilation should be provided
to maintain generator compartment
temperature below 122oF (50°C)
General - 3 Phase
12.5 KW- 60 Hertz
9.3 KW- 50 Hertz
Voltage - 3 Phase
(60 Hertz)
Voltage - 3 Phase
(50 Hertz)
Amperage - 3 Phase
(60 Hertz)
Amperage - 3 Phase
(50 Hertz)
Generator Cooling
Air Requirements
(60 Hertz)
at
1800 rpm
Generator Compartment
Ambient Temperature
Recommendations
SPECIFICATIONS 15 EGTD
Brushless six pole, revolving field. Sealed
lubricated single bearing design. 12 Lead
reconnectable for low voltage WYE, high
voltage Delta. Solid State voltage regulator
with protection circuitry.
Low voltage WYE
208 volts
High voltage WYE
480 volts
DELTA
240 volts
High voltage WYE
380 volts
DELTA
230 volts
Low voltage WYE
43Amps
High voltage WYE
17 Amps
DELTA
37 Amps
High voltage WYE
17 Amps
DELTA
30 Amps
225 - 250 elm (5.66 - 6.37 cmm)
NOTE:
Increase air supply 15% tor 50 Hertz
operation (1500 rpm)
122"F (50°C) maximum
NOTE:
Forced ventilation should be provided
to maintain generator compartment
temperature below122'F (SOOC)
AC GENERATOR (Single Phase)
AC GENERATOR (3 Phase)
Single Phase
Voltage
Voltage regulation:
Frequency regulation:
Rating (Volts AC)
60 Hertz (1800 rpm)
50 Hertz (1500 rpm)
Generator Cooling
Air Requirements
(60 Hertz)
at
1800 rpm
Engine Combustion Air
Requirements @60Hz
1800 rpm
Generator Compartment
Ambient Temperature
Recommendations
Brushless, four-pole, revolving field.
Pre-lubricated, single bearing design.
Reconnectable, single phase transformer
regulation (optional solid-state voltage
regulation) ..
120 or 120/240 Volts - 60 Hertz
230 Volts - 50 Hertz
± 5% no load to full load.
±3 Hertz (5%) no load to lull load.
(Electronic Governered)
Non-Electric ± 3 Hertz
120 Volts
125 Amps
120/240 Volts
195.8/49.9 Amps
230 Volts
, 60 Amps
225- 250 cfm (6.37 - 705 cmm)
NOTE:
Increase air supply 15% tor 50 Hertz
operation (1500 rpm)
46 elm (1.9 cmm)
122°F (so·c) maximum
NOTE:
Forced ventilation should be provided
to maintain generator compartment
temperature below122'F (50•C)
General - 3 Phase
15.0 KW- 60 Hertz
12.0 KW- 50 Hertz
Voltage - 3 Phase
(60 Hertz)
Voltage - 3 Phase
(50 Hertz)
Amperage - 3 Phase
(60 Hertz)
Amperage - 3 Phase
(50
Hertz)
Generator Compartment
Ambient Temperature
Recommendations
Engfnes & Generators
45
Brush less six pole, revolving field. Sealed
lubricated single bearing design. 12 Lead
reconnectable for low voltage WYE, high
voltage Delta. Solid State voltage regulator
with protection circuitry.
Low voltage WYE
208 volts
High voltage WYE
480 volts
DELTA
240 volts
High voltage WYE
400 volts
DELTA
230 volts
Low voltage WYE
52 Amps
High voltage WYE
22 Amps
DELTA
45 Amps
High voltage WYE
22Amps
DELTA
39Amps
122°F (5o•c) maximum
NOTE:
Forced ventilation should be provided
to maintain generator compartment
temperature below122'F (50,G)