Pressure transmitter with 4-20 ma hart protocol (revision 5 and 7)
Hide thumbs Also See for Rosemount 3051P:
Table of Contents

Advertisement

May 2019
Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std C22.2 No.
Markings:
9.3
Europe
E1 ATEX Flameproof
Certificate: KEMA97ATEX2378X
Standards: EN 60079-0:2012 + A11:2013, EN60079-1:2014,
Markings:
Table 9-1: Process Connection Temperature
Temperature class Process connection
T6
T5
T4
1. This device contains a thin wall diaphragm less than 1 mm thickness
that forms a boundary between zone 0 (process connection) and
zone 1 (all other parts of the equipment). The model code and
datasheet are to be consulted for details of the diaphragm material.
Installation, maintenance and use shall take into account the
environmental conditions to which the diaphragm will be subjected.
The manufacturer's instructions for installation and maintenance
shall be followed in detail to assure safety during its expected
lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
Quick Start Guide
25-1966, CSA Std C22.2 No. 30-M1986, CAN/CSA-C22.2 No.
94-M91, CSA Std C22.2 No. 142-M1987, CAN/CSA-C22.2 No.
157-92, CSA Std C22.2 No. 213-M1987, ANSI-
ISA-12.27.01-2003
Intrinsically Safe Class I, Division 1 when connected in
accordance with Rosemount drawing 02088-1024,
Temperature Code T4; Ex ia; Type 4X; Factory Sealed; Single
Seal
EN60079-26:2015
II 1/2 G Ex db IIC T6....T4, Ga/Gb, T6(–60 °C ≤ T
T5/T4 (–60 °C ≤ T
a
temperature
–60 to +70 °C
–60 to +80 °C
–60 to +120 °C
≤ +80 °C)
Ambient temperature
–60 to +70 °C
–60 to +80 °C
–60 to +80 °C
Quick Start Guide
≤ +70 °C),
a
25