6.3 Electrical Data

6.3.1 Air Handling Units

MIN. POWER SUPPLY
GOLD 004:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT
GOLD 005, capacity variant 1:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT
GOLD 005, capacity variant 2:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT
GOLD 007, capacity variant 1:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT
GOLD 007, capacity variant 2:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT
GOLD 008, capacity variant 1:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT
GOLD 008, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 011, capacity variant 1:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT
GOLD 011, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 012–035:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 040, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 16 AT
GOLD 040, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 20 AT
GOLD 050, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 16 AT
GOLD 050, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 20 AT
GOLD 060, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 16 AT
GOLD 060, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 25 AT
GOLD 070, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 16 AT
GOLD 070, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 25 AT
GOLD 080, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 25 AT
GOLD 080, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 40 AT
GOLD 100, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 25 AT
GOLD 100, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 40 AT
GOLD 120, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 40 AT
GOLD 120, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 63 AT
We reserve the right to alter specifications.

6.3.2 Fans

RATED DATA PER FAN
GOLD 004:
Motor shaft power: 0.8 kW (0.41 kW)*,
motor controller: 1 x 230 V, 50 Hz
GOLD 005:
Motor shaft power: 0.8 kW,
motor control system, 1 x 230 V, 50 Hz
or
Motor shaft power: 1.15 kW,
motor controller: 1 x 230 V, 50 Hz
GOLD 007:
Motor shaft power: 0.8 kW,
motor control system, 1 x 230 V, 50 Hz
or
Motor shaft power: 1.15 kW,
motor controller: 1 x 230 V, 50 Hz
GOLD 008:
Motor shaft power: 1.15 kW,
motor control system, 1 x 230 V, 50 Hz
or
Motor shaft power: 1.6 kW,
3 x 400 V, 50 Hz
GOLD 011:
Motor shaft power: 1.15 kW,
motor control system, 1 x 230 V, 50 Hz
or
Motor shaft power: 1.6 kW,
3 x 400 V, 50 Hz
GOLD 012:
Motor shaft power: 1.6 kW,
motor control system, 3 x 400 V, 50 Hz
or
Motor shaft power: 2.4 kW,
motor control system, 3 x 400 V, 50 Hz
GOLD 014:
Motor shaft power: 1.6 kW,
motor control system, 3 x 400 V, 50 Hz
or
Motor shaft power: 2.4 kW,
motor control system, 3 x 400 V, 50 Hz
GOLD 020:
Motor shaft power: 2.4 kW,
motor control system, 3 x 400 V, 50 Hz
or
Motor shaft power: 3.4 kW,
motor control system, 3 x 400 V, 50 Hz
GOLD 025:
Motor shaft power: 2.4 kW,
motor control system, 3 x 400 V, 50 Hz
or
Motor shaft power: 3.4 kW,
motor control system, 3 x 400 V, 50 Hz
GOLD 030:
Motor shaft power: 4.0 kW,
motor control system, 3 x 400 V, 50 Hz
or
Motor shaft power: 5.0 kW,
motor control system, 3 x 400 V, 50 Hz
GOLD 035:
Motor shaft power: 4.0 kW,
motor control system, 3 x 400 V, 50 Hz
or
Motor shaft power: 5.0 kW,
motor control system, 3 x 400 V, 50 Hz
GOLD 040:
Motor shaft power: 6.5 kW,
motor control system, 3 x 400 V, 50 Hz
or
Motor shaft power: 10 kW,
motor control system, 3 x 400 V, 50 Hz
GOLD 050:
Motor shaft power: 6.5 kW,
motor control system, 3 x 400 V, 50 Hz
or
Motor shaft power: 10 kW,
motor control system, 3 x 400 V, 50 Hz
GOLD 060:
Motor shaft power: 2 x 4.0 kW,
motor control system, 3 x 400 V, 50 Hz
or
Motor shaft power: 2 x 6.5 kW,
motor control system, 3 x 400 V, 50 Hz
GB.GOLDSKFSD.190515