Technical data

Output (ERP):
Frequency band:
Temperature sensor:
Pressure sensor:
With SMA
VOC sensor
RH sensor:
IP class:
Corrosivity class:
Pressure class:
Air tightness class, casing:
Air tightness class circular damper,
closed:
Air tightness class rectangular
damper, closed:
Running time open/close (90°):
Spring return actuator, running
time electricity (90°):
Return time spring:
Ambient temperature
Operation:
Storage:
RH:
CE marking:

Electrical data

Power supply:
Connections pipe dim.
Power:
Valve actuator:
Max. power consumption:
Variant
Motor
5 Nm
Normal
10 Nm
15 Nm
5 Nm
Spring return
10 Nm
20 Nm
8
Swegon reserves the right to alter specifications.
50 mW
2.45 GHz, IMS band
(2400--2483 MHz)
0 - 50°C ± -0.5°C
0 - 300 Pa
450 - 2000 ppm
0 - 100 RH%
120 s
120 s
max. 20 s (90°)
0 – 50°C
-20 – +50°C
10 - 95%
(non-condensing)
2016/42/EC (MD)
2014/53/EU (RED)
2011/65/EU (RoHS)
24V AC ±15% 50 - 60Hz
Screw terminal max. 2.5mm
Push-in spring force connections,
max. 1.5 mm
See table below
VA
+1 valve
+2 valve
Default
actuator
actuator
8
15
22
12
19
16
23

Declaration of Conformity

Swegon AB hereby affirms that
WISE Damper with integrated radio, complies with the
essential characteristic demands and relevant regulations
specified in the following directives: 2006/42/EC (MD),
2014/53/EU (RED) and 2011/65/EU (RoHS2):
The following standards have been observed:
EN ISO 12100:2010
IP20
C3
EN 60204-1:2006
A
EN 60730-1:2011
C
4
EN 60730-2-14:2009
3
IEC 60529:1992+A2:2013
EN 61000-6-2:2007
EN 61000-6-3:2007
EN 300328 V1.9.2, V1.9.1,
V1.8.1
Person responsible for this declaration:
Name: Ingvar Hagström, Factory Manager Tomelilla
Address: Industrigatan 5, 273 21 Tomelilla, Sweden
Date: 170131
This declaration is applicable only if the product has been
installed according to the instructions in this document and
2
if no modifications or changes have been made on this
product.
2
References
www.swegon.com
Building Materials Declaration
WISE Damper product data sheet
WISE System Guide
SuperWISE II / SuperWISE II SC User Manual
WISE Project Planning Guide VS & Cooling, Electric &
Control and Ventilation
20180620
Safety of machinery - General principles for
design - Risk assessment and risk mitigation
Safety of machinery - Electrical equipment of
machines - Part 1: Generic standards
Automatic electrical controls for household
and similar use - Part 1 Generic standards
Automatic electrical controls for household
and similar use - Part 2 Particular require-
ments for electric actuators
Degrees of protection provided by enclosures
(IP code)
Electromagnetic compatibility (EMC). Generic
standards. Immunity for industrial environ-
ments
Electromagnetic compatibility (EMC). Generic
standards. Emission standard for residential,
commercial and light-industrial environments
Electromagnetic compatibility and Radio spec-
trum Matters (ERM) - Wideband Transmis-
sion systems - Data transmission equipment
operating in the 2.4 GHz ISM band and using
spread spectrum modulation techniques

Advertisement