Siemens
Building Technologies
4.2.3

Parameter setting

Start with quick commissioning according the commissioning guide
CM1G5192. It is very important to enter the right motor data!
Par. Nr.
Value
P0003
3
P0702(0)
99
P0702(1)
99
P1000(0)
23
P1001
40
P1074(0)
722.1
P1074(1)
722.1
P1270(0)
722.1
P1270(1)
722.1
P1271(0)
P1271(1)
For further information please see also Chapter 5 – Commissioning Wizard for
Essential Service Mode.
4.2.4

Remarks

• The hand mode will be disabled automatically when ESM is active.
• The information "drive fault" and "drive running" is still available on the 2 relay
outputs.
On demand the information "ESM active" can be configured to a relay output.
Application Guide «Fire Mode»
Application Examples
Parameter function
User access level 3
Function of DIN2 in „Auto"
mode
Function of DIN2 in „Hand"
mode
Setpoint source in Auto
Fixed frequency when ESM is
active
Disable Additional Setpoint in
Auto
Disable Additional Setpoint in
Hand
Activate ESM in Auto
Activate ESM in Hand
Activation of ESM control word
Enable FF in ESM mode
Function selection
Expert access
BICO = free parame-
terization
BICO = free parame-
terization
AI1 + FF
in Hz
Disable AI1
Disable AI1
DI2
DI2
press▼once;
will appear and ESM
control word is acti-
vated
press▲once
17 / 44
CM1A5192en_01
23.10.2007