PID Control in ESM/Fire Mode

It is possible to configure PID Control as follows:
Standard Mode
ESM/Fire Mode
Yes
Yes
No
No
6.5.1

PID Control in both ESM and Standard Mode

Normal operation mode PID control should be configured as described in the
Commissioning Guide.
P2200 in000/in001= 1.0 or whatever the source is.
P22xx~P23xx PID parameters set as per application ESM/Fire Mode:
Parameter
Index
P0003
-
P1271
in001
P2xxx
Display of P1271 in001 (ESM Control word 2) on the BOP
Alternatively, use EasyComm to set the correct bit.
Application Guide «Fire Mode»
Essential Service Mode (in-depth information)
Chapter
Yes
6.5.1
No
6.5.2
Yes
6.5.3
No
6.5.4
Default Set to Function and description
1
3
Access Level
Set access level to Expert
ESM Control word1
Activate bit 08 and de-activate bi12 to enable PID in ESM
Configure PID related parameters
P2201~P23xx accordingly to application