5.1.4

Mounting

The braking resistor for all modules is connected at terminals DCP/R1 and R2. Since it generates heat, it
should be mounted to the side of the Power Modules.
The braking resistors for the PM340 Power Modules in frame sizes FSA and FSB are designed as base
components. If the PM340 Power Modules of the FSA or FSB frame size are operated without a line reactor,
the braking resistors can also be installed under the Power Modules.
The braking resistors for the PM340 Power Modules of the FSC to FSF frame sizes should be placed outside
the control cabinet or the switchgear room to lead the resulting heat loss away from the Power Modules. This
reduces the level of air conditioning required.
The braking resistors can be installed horizontally or vertically. The power connections on vertically installed
resistors, must be at the bottom.
5.1.5

Technical data

Table 11 Technical data of braking resistors for PM340 Power Modules, frame sizes FSB, FSC
Order number
Suitable for Power Modules of
frame size
Resistance
Unit rating PDB
Peak power Pmax
Load duration for peak power Ta
Period duration of braking duty
cycle T
Degree of protection
Power connections (including PE)
Thermostatic switch (NC contact)
Maximum contact load
connecting cable
Weight
For information about order numbers, refer to SIEMENS manual
¹) Power Modules Blocksize, 1-phase AC
²) Power Modules Blocksize, 3-phase AC
Siemens S120_EN_rev06-08062017.docx
6SL3201-0BE12-0AA0
FSB ²)
Ω
160
kW
0.2
kW
4.0
s
12.6
s
252
IP20 or IPXXB
Pigtail
3 x 1.5 mm2
shielded, length
0.5 m
250 VAC / 2.5
A
kg
1.6
6SE6400-4BD16-5CA0
FSC ²)
56
0.65
13
13.1
262
IP20 or IPXXB
Pigtail
3 x 1.5 mm2
shielded, length
0.9 m
250 VAC / 2.5
A
3.8
5-4