Ordering Numbers: Brake Resistors 10 - Danfoss VLT FC 360 Design Manual

Automationdrive
Table of Contents

Advertisement

Type Code and Selection

5.3.1 Ordering Numbers: Brake Resistors 10%

FC 360
P
R
m (HO)
min
T4
[kW]
[Ω]
HK37
0.37
890
HK55
0.55
593
HK75
0.75
434
H1K1
1.1
288
H1K5
1.5
208
H2K2
2.2
139
H3K0
3
100
H4K0
4
74
H5K5
5.5
54
H7K5
7.5
38
H11K
11
27
H15K
15
19
H18K
18.5
16
H22K
22
16
H30K
30
11
H37K
37
9
H45K
45
8
H55K
55
6
H75K
75
4
Table 5.4 FC 360 - Mains: 380-480 V (T4), 10% Duty Cycle
®
VLT
AutomationDrive FC 360 Design Guide
R
R
P
br. nom
rec
br avg
[kW]
[Ω]
[Ω]
1041.98
989
0.030
693.79
659
0.045
508.78
483
0.061
338.05
321
0.092
244.41
232
0.128
163.95
155
0.190
118.86
112
0.262
87.93
83
0.354
63.33
60
0.492
46.05
43
0.677
32.99
31
0.945
24.02
22
1.297
19.36
18
1.610
18.00
17
1.923
14.58
13
2.576
11.71
11
3.206
9.58
9
3.921
7.80
7
4.816
5.68
5
6.612
®
MG06B202 - VLT
is a registered Danfoss trademark
Code no.
Period
Cable cross
section
175Uxxxx
[s]
[mm
2
]
3000
120
1.5
3001
120
1.5
3002
120
1.5
3004
120
1.5
3007
120
1.5
3008
120
1.5
3300
120
1.5
3335
120
1.5
3336
120
1.5
3337
120
1.5
3338
120
1.5
3339
120
1.5
3340
120
1.5
3357
120
1.5
3341
120
2.5
3359
120
2.5
3065
120
4
3070
120
6
3231
120
10
Therm.
Max. brake
relay
torque
2
*
with R
*
rec
[A]
[%]
0.3
139
0.4
131
0.4
129
0.5
132
0.8
145
0.9
131
1.3
131
1.9
128
2.5
127
3.3
132
5.2
130
6.7
129
8.3
132
10.1
128
13.3
150
15.3
146
20
150
26
150
36
150
65
5
5

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT FC 360 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Vlt automationdrive fc 360

Table of Contents