HOW TO DO QUICK TEST

Function: To test installation quickly and easily. The installed device can be activated and NACs can be
activated for a short period of time. The quick test menu allows user to configure quick test parameters. User
can stop the quick test manually. Quick test mode will automatically quit when the quick test time is out.
The following parameters can be configured before doing quick test:
Parameters
Set the time interval of system quick test. The FACP
will quit automatically Quick Test mode after the
Quick Test Time
configured time is expired . When quick test ends,
FACP will reset all events automatically.
Set if the output is disabled during quick test. If it is
configured as True, FACP will not activate any output
Disable Output
on events in Quick Test mode. If it is configured as
False, output can be activated manually or
automatically in Quick test mode.
Set if the annunciator is off during quick test. If it is
configured as True, no events in Quick Test mode will
Annunciator Off
be forwarded to annunciators. If it is configured as
False, events in Quick Test mode will be forwarded to
annunciators as configured.
Set if the history is off during quick test. If it is
configured as True, no events in Quick Test mode will
History Off
be recorded in history. If it is configured as False,
events in Quick Test mode will be recorded in history.
Set if the NAC is off during quick test. If it is
configured as True, NAC shall not respond to any
NAC Off
events in Quick Test mode. If it is configured as
False, NAC shall respond as configured in Quick Test
mode.
Programming Manual of FC2005/FC901
Description
Value
Default
{min: 5 ;max: 30;}
{True;False;}
{True;False;}
False
{True;False;}
False
{True;False;}
False
30
True
Page: 14/48