Siemens FC2005 Programming Manual page 39

Fire alarm control panel
Table of Contents

Advertisement

8726
Name
Address
Silenceable
(channel)
HoldThroughReset
(channel)
OOH941
Name
Address
LED normal off
Multi Critieria Usage
(channel)
Photoelectric Setting
(channel)
Thermal Alarm
Usage
(channel)
Thermal Alarm
Setting
(channel)
OOHC941
Name
Address
LED normal off
Multi Critieria Usage
(channel)
Programming Manual of FC2005/FC901
Bool: True (default)/ False
Bool: True/ False (default)
Bool: True/ False (default)
Option 1: ASD (default)
Option 2: Photoelectric(alarm)
Option 3: Off
Option 1: 2.50%/ft Threshold
Option 2: 3.00%/ft Threshold
Option 3: 3.50%/ft Threshold
Option 4: 2.50%/ft Threshold Verified
Option 5: 3.00%/ft Threshold Verified
Option 6: 3.50%/ft Threshold Verified
Option 1: Thermal Evaluation(default)
Option 2: Off
Option 1: Fixed temperature 135°F
Option 2: Fixed temperature 145°F
Option 3: Fixed temperature 155°F
Option 4: Fixed temperature 165°F
Option 5: Fixed temperature 175°F(default)
Option 6: Fixed temperature 135°F + ROR 15°F
Option 7: Fixed temperature 175°F + ROR 15°F
Option 8: Fixed temperature 135°F + ROR 20°F
Option 9: Fixed temperature 175°F + ROR 20°F
Bool: True/ False (default)
Option 1: ASD (default)
Option 2: Photoelectric(alarm)
Option 3: Off
Page: 38/48

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc901

Table of Contents