Siemens FC2005 Programming Manual page 41

Fire alarm control panel
Table of Contents

Advertisement

ASD Setting
Thermal Alarm
Usage
(channel)
Thermal Alarm
Setting
(channel)
FDOOTC441
Name
Address
LED normal off
Multi Critieria Usage
(channel)
Programming Manual of FC2005/FC901
Option 1: Telecommunication
Option 2: Incipient
Option 3: Ion equivalent
Option 4: Data Center
Option 5: Computer Room
Option 6: Precious Storage
Option 7: Power Generation
Option 8: Hospital
Option 9: Health Care
Option 10: Dormitory
Option 11: Utility Room
Option 12: Lobby
Option 13: Office
Option 14: Hotel
Option 15: School
Option 16: Warehouse
Option 17: Manufacturing
Option 18: Parking Garage
Option 19: Open Environment
Option 20: EMI noise
Option 21: Hostile
Option 22: Duct
Option 1: Thermal Evaluation(default)
Option 2: Off
Option 1: Fixed temperature 135°F
Option 2: Fixed temperature 145°F
Option 3: Fixed temperature 155°F
Option 4: Fixed temperature 165°F
Option 5: Fixed temperature 175°F(default)
Option 6: Fixed temperature 135°F + ROR 15°F
Option 7: Fixed temperature 175°F + ROR 15°F
Option 8: Fixed temperature 135°F + ROR 20°F
Option 9: Fixed temperature 175°F + ROR 20°F
Bool: True/ False (default)
Option 1: ASD (default)
Option 2: Photoelectric(alarm)
Option 3: Off
Page: 40/48