Siemens FC2005 Programming Manual page 4

Fire alarm control panel
Table of Contents

Advertisement

DACT: The Digital Alarm Communication Transmitter board which will send control panel status data to a
remote receiving station.
DACT Connection: DACT has two physical connections to PSTN, two telephone lines. One is the
main connection and the other is used as backup connection.
DACT Network: The DACT has two accounts and each account can be configured separately.
Serial Interface Circuit: The module can drive up to 8 remote LCD annunciators by Universal Fire
Protocol.
Detection tree:
The Detection tree contains the zones used for report different types of events. The supported zone types
include:
Manual alarm zone
Auto alarm zone
Waterflow zone
Supervisory zone
Trouble zone
Status zone
AC Fail zone
There are two default zones:
New Manual Alarm Zone1:
New Auto Alarm Zone1:
The system will create a new zone for each new added channel automatically. User can add or delete the
zones except the two default zone at will. If user deleted a zone, the channels in the zone will be reassigned
to the default zone according to the types.
Control tree:
The control tree contains all control logics. The causes of the control logic can be the control panel, zones
and channels. The effects should be outputs, relays and NACs.
There are two default control logic:
Control 1: There is no device in the cause and the effect is programmable relay.
Adv. Control 1: The cause of the logic is the control panel. This control logic is used to realize the
conditional activation of the City Tie, Lease Line, alarm/supervisory/trouble relays and the NACs.
The criteria is configured at devices in effect.
Dialer Group:
The dialer group is only used for sending information through DACT. Dialer group groups events of the zones
which assigned to it and report events as it self's. This means if multiple children report the same kind of
events, dialer group will only report it once. Similarly, the restoral events should be sent only when all zones in
the group restore this kind of events.
There is one default dialer group:
New Dialer Group 1. The system will assign the default zones and every new created zone to the
default dialer group.
Programming Manual of FC2005/FC901
Page: 3/48