Technical Maintenance And Design Data - Wolf CGB-2 Series Installation Instructions For Contractors

Wall mounted gas condensing boiler/gas condensing combi boiler
Hide thumbs Also See for CGB-2 Series:
Table of Contents

Advertisement

NTC
Sensor resistances
Temp. °C
Resist. Ω
-17
40,810
-16
38,560
-15
36,447
-14
34,463
-13
32,599
-12
30,846
-11
29,198
-10
27,648
-9
26,189
-8
24,816
-7
23,523
-6
22,305
-5
21,157
-4
20,075
-3
19,054
-2
18,091
-1
17,183
0
16,325
1
15,515
2
14,750
3
14,027
4
13,344
5
12,697
6
12,086
7
11,508
8
10,961
9
10,442
10
9952
11
9487
12
9046
13
8629
14
8233
15
7857
16
7501
Connection types
Type
1)
Open flue
B23, B33, C13x,
C33x, C43x, C53,
C53x, C83x, C93x
Marking "x" indicates that all components of the flue gas route are surrounded by combustion air.
1)
In Switzerland, observe the G1 gas guidelines.
2)
88
40. Technical maintenance and design
data
Boiler water temperature sensor, cylinder temperature sensor, DHW outlet temperature
sensor, outside temperature sensor, return temperature sensor, eHLSC sensor, flue gas
temperature sensor, header temperature sensor.
Temp. °C
Resist. Ω
17
7162
18
6841
19
6536
20
6247
21
5972
22
5710
23
5461
24
5225
25
5000
26
4786
27
4582
28
4388
29
4204
30
4028
31
3860
32
3701
33
3549
34
3403
35
3265
36
3133
37
3007
38
2887
39
2772
40
2662
41
2558
42
2458
43
2362
44
2271
45
2183
46
2100
47
2020
48
1944
49
1870
50
1800
Operating mode
Room-
sealed
moisture resistant
X
X
B33, C53, C83x
Temp. °C
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
Can be connected to
Chimney,
Air/flue gas
chimney
C43x
Resist. Ω
Temp. °C
1733
85
1669
86
1608
87
1549
88
1493
89
1438
90
1387
91
1337
92
1289
93
1244
94
1200
95
1158
96
1117
97
1078
98
1041
99
1005
100
971
101
938
102
906
103
876
104
846
105
818
106
791
107
765
108
740
109
716
110
693
111
670
112
649
113
628
114
608
115
589
116
570
117
552
118
Balanced
Certified
flue
rm. sealed
balanced
flue
C13x
,
C63x
2)
C33x, C53x
Resist. Ω
535
519
503
487
472
458
444
431
418
406
393
382
371
360
349
339
330
320
311
302
294
285
277
270
262
255
248
241
235
228
222
216
211
205
Moisture-
resistant flue
B23, C53x,
C83x, C93x
3064810_201804

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents