Wolf CGB-2 Series Installation Instructions For Contractors page 44

Wall mounted gas condensing boiler/gas condensing combi boiler
Hide thumbs Also See for CGB-2 Series:
Table of Contents

Advertisement

Parameter HG15
Cylinder hysteresis
Factory setting: see table
Setting range: 1 to 30 K
Individual setting:_____
Parameter HG16
Pump rate HC, minimum
Factory setting: see table
Setting range: 15 to 100 %
Individual setting:_____
Parameter HG17
HC pump rate, maximum
Factory setting: see table
Setting range: 15 to 100 %
Individual setting:_____
Parameter HG19
Run-on time, CLP
(cylinder loading pump)
Factory setting: see table
Setting range: 1 to 10 min
Individual setting:_____
44
24. Parameter description
The cylinder hysteresis regulates the start point for cylinder heating.
The higher the setting, the lower the start point for cylinder heating.
Example: Set cylinder temperature 60 °C
Cylinder hysteresis 5 K
Cylinder heating commences at 55 °C and ends at 60 °C.
In heating mode, the internal appliance pump does not regulate below this set
value. Independent of pump control type set in HG37.
In heating mode, the internal appliance pump does not regulate above this set
value. Independent of pump control type set in HG37. If the pump control type
is "Constant", HG17 is used as the setting for the pump speed in heating mode.
After completing cylinder heating in summer mode (the cylinder has reached
the set temperature), the cylinder primary pump will run on up to the maximum
set run-on time.
The cylinder primary pump will switch OFF prematurely if, during the run-on
time, the boiler water temperature cools down to a differential between boiler
and set cylinder temperature of 5 K.
In winter mode, the cylinder primary pump runs on for a fixed time of 30 seconds
after successful cylinder heating (regardless of parameter HG19).