Saunders CRANE I-VUE Quick Start Manual page 12

Intelligent sensing technology

Advertisement

Saunders® I-VUE
Note: This guide only details self-calibration at the I-VUE unit.
For calibration via a network, please refer to full IOM manual.
Minimum required valve travel: 3mm
3)
The smart window will then read "SURE".
This is a positive confirmation check that
you want to perform self-calibration routine
4)
To confirm self-calibration routine hold the green S side of the magnetic key
over S2 for a few seconds. The I-VUE will begin to perform self-calibration
routine.
5)
After self-calibration the ring of LED's will flash green and the I-VUE will return
to normal operating mode.
6)
To cancel self-calibration, when the screen reads "SURE" hold the black N side
of the magnetic key over N3 for a few seconds and the I-VUE will return to
normal operating mode
Self-Calibration
1)
Hold the black N side of the magnetic key
over N3. The LED indicator will light-up red.
2)
After a few seconds the smart window will
read "SELF CALIBRATION"
Rev 1.00
(Integral Solenoid)
www.cranechempharma.com
www.saundersI-VUE.com
12