3.3.2 Mechanical

Output: Double insulated 5 ft (1.5m) lead with safety banana plugs
Zero Adjustment: ± 10A approx. by 10 turn knob at base of case
Case Protection: IP30 per IEC 529
Drop Test: 1.0m on 38mm of oak on concrete; test according to EN 61010
Mechanical Shock: 100G, test per IEC 68-2-27
Vibration: Test per IEC 68-2-6
Frequency Range: 5 to 15Hz, Amplitude: 1.5mm
Handle: UL 94 V0
Jaws: UL 94 V0
3.3.3 Environmental
Operating Temperature Range: 14° to 131°F (-10° to +55°C)
Storage Temperature Range: -40° to 176°F (-40° to +80°C)
Temperature Influence: ≤ 300° ppm/°K or 1%/10°K
Operating Relative Humidity:
10° to 35°C: 90 ± 5% RH (without condensation)
40° to 55°C: 70 ± 5% RH (without condensation)
Humidity Influence: 10 to 90% RH @ reference temperature ≤ 0.1% R
Altitude: Operating: 0 to 2000m

3.3.3 Safety

Electrical:
EN 61010-2-32, 600V CAT III, Pollution: 2
Electromagnetic Compatibility:
EN 50081-1 Class B
EN 50082-2 Electrostatic discharge IEC 1000-4-2
Radiated field IEC 1000-4-3
Fast transients IEC 1000-4-4
Magnetic field at 50/60 Hz IEC 1000-4-8
AC/DC Current Probe Models MR410 and MR520
Find Quality Products Online at:
All manuals and user guides at all-guides.com
15 to 25Hz, Amplitude: 1mm
25 to 55Hz, Amplitude: 0.25mm
≤ 0.2A/°K on Zero
Non-operating: 0 to 12,000m
GlobalTestSupply
www.
.com
sales@GlobalTestSupply.com
11