Article number
Input ranges (rated values), resistors
0 to 150 ohms
•
Input resistance (0 to 150 ohms)
•
0 to 300 ohms
•
Input resistance (0 to 300 ohms)
•
Cable length
shielded, max.
•
Analog value generation for the inputs
Measurement principle
Integration and conversion time/resolution per
channel
Resolution with overrange (bit including
•
sign), max.
Integration time, parameterizable
•
Integration time (ms)
•
Interference voltage suppression for inter-
•
ference frequency f1 in Hz
Conversion time (per channel)
•
Smoothing of measured values
parameterizable
•
Step: None
•
Step: low
•
Step: Medium
•
Step: High
•
Encoder
Connection of signal encoders
for voltage measurement
•
for current measurement as 2-wire trans-
•
ducer
for current measurement as 4-wire trans-
•
ducer
for resistance measurement with two-wire
•
connection
for resistance measurement with three-wire
•
connection
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
Manual, 08/2018, A5E32350124-AD
6ES7144-5KD00-0BA0
Yes
10 MΩ
Yes
10 MΩ
30 m
integrating
16 bit
Yes; channel by channel
0,3 / 16,7 / 20 / 60
3 600 / 60 / 50 / 16.7
2 / 18 / 21 / 61 ms
Yes
Yes; 1x cycle time
Yes; 4 x cycle time
Yes; 16 x cycle time
Yes; 32 x cycle time
Yes
Yes
Yes
Yes
Yes
Technical specifications
39