Siemens SIMATIC ET 200AL Manual page 37

Simatic analog input module ai 4xu/i/rtd 4xm12 (6es7144-5kd00-0ba0)
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Interrupts/diagnostics alarms
5.3 Diagnostics alarms
Table 5- 8
Diagnostics
alarm
Wire break
High limit violat-
ed
Low limit violated 8
Parameter error
Hardware inter-
rupt lost
36
Diagnostics alarms - for the measuring range: Pt100 and Ni100
Error code
Meaning
6
Impedance of encoder circuit too
H
high
Wire break between the module
and sensor
Channel not connected (open)
7
Value is above overrange.
H
Value is below underrange.
H
10
Module parameter assignment is
H
faulty
16
At least one hardware interrupt
H
could not be signaled because
too many hardware interrupts are
pending.
Remedy
Use a different encoder type or
modify the wiring, for example,
using cables with larger cross-
section
Connect the cable
Correct interplay between mod-
ule and sensor
Correct interplay between mod-
ule and sensor
Correct the parameter assign-
ment
Correct the program or the pro-
cess
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
Deactivate diagnostics
Connect the channel
Deactivate channel
Manual, 08/2018, A5E32350124-AD