Technical specifications
Article number
Encoder supply
Number of outputs
24 V encoder supply
Short-circuit protection
•
Output current, max.
•
Power loss
Power loss, typ.
Analog inputs
Number of analog inputs
For current measurement
•
For voltage measurement
•
For resistance/resistance thermometer
•
measurement
permissible input voltage for voltage input
(destruction limit), max.
permissible input current for current input (de-
struction limit), max.
Cycle time (all channels), min.
Technical unit for temperature measurement
adjustable
Input ranges (rated values), voltages
0 to +10 V
•
Input resistance (0 to 10 V)
•
1 V to 5 V
•
Input resistance (1 V to 5 V)
•
Input ranges (rated values), currents
0 to 20 mA
•
Input resistance (0 to 20 mA)
•
4 mA to 20 mA
•
Input resistance (4 mA to 20 mA)
•
Input ranges (rated values), resistance thermome-
ter
Ni 100
•
Input resistance (Ni 100)
•
Pt 100
•
Input resistance (Pt 100)
•
38
6ES7144-5KD00-0BA0
4
Yes; per channel, electronic
0.5 A; per channel, total current of all channels
max. 1 A
1.5 W
4
4
4
4
30 V
50 mA
8 ms
Yes; Degrees Celsius / degrees Fahrenheit /
Kelvin
Yes
10 MΩ
Yes
10 MΩ
Yes
50 Ω
Yes
50 Ω
Yes; Standard/climate
10 MΩ
Yes; Standard/climate
10 MΩ
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
Manual, 08/2018, A5E32350124-AD