3SK1 devices
5.3 3SK1 output expansions
5.3.6

Output expansion 3SK1213

5.3.6.1

Device features

MLFB:
3SK1213-xAB40
3SK1213-xAJ20
3SK1213-xAL20
(x) 1 = screw-type terminal; 2 = spring-loaded terminal
Supply:
24 V DC:
● An SELV / PELV power supply must be used for the infeed
115 V AC and 230 V AC
● Direct line supply connection L/N
Device properties:
● Slide switch for selecting the activation type (time-delayed / instantaneous)*
● 1 LED for status display
● 3 enabling circuits (safe circuits, NO contacts)
● 1 NC circuit as feedback contact for output expansion 3SK1213 for the up-circuit basic
unit
● 3ZY device connectors*
● Enclosure width 90 mm
● Removable terminals
* For 24 V DC variant only
When using 3ZY device connectors
The output expansion 3SK1213 must always be terminated with a device termination
connector, type 2, set for enclosures > 45 mm (3ZY1212-0FA01). Expansion on the right-
hand side is then no longer possible.