3SK1 devices
5.2 3SK1 Advanced
5.2.5

Functions

Table 5- 3
DIP switch
Autostart
Cross-circuit detection deactivated
2 x single-channel sensor connection
Start-up test ON
In the delivery state, all the DIP switches are in switch position: right.
Terminal parameterization:
Jumper on terminals T1/PAR = NO/NC evaluation
Table 5- 4
SET/RESET button
Function of the
SET/RESET button
SET
RESET
Note
The SET/RESET pushbutton only triggers a reset for the device on which the button is
pressed.
58
Switch position: left Schematic
Status of the indicating LEDs
"DEVICE" LED flashing yellow
"DEVICE" LED red
"DEVICE" LED flashing green yellow
"SF" LED red
DIP switch
Switch position: right
No.
1
Monitored start
2
Cross-circuit detection activated
3
1 x two-channel sensor connection
4
Start-up test OFF
Function
Press key for about 1 s
The parameterization is loaded
Press key for about 1 s
=> The device restarts without the supply voltage
having to be switched off
Manual, 04/2013, A5E02526190021A/RS-AA/01