Switching capacity current of the NO contacts of
the relay outputs
at DC-13
at 24 V
at 115 V
at 230 V
at AC-15
at 115 V
at 230 V
Switching capacity current of the NC contacts of
the relay outputs
at DC-13
at 24 V
at 115 V
at 230 V
at AC-15
at 115 V
at 230 V
Thermal current of the contact-affected switching
element maximum
Total current maximum
Mechanical operating cycles as operating time
typical
Max. permissible voltage for safe isolation
between electronic evaluation device and
enabling circuit according to EN 60947-1
Design of the fuse link for short-circuit protection
of the NO contacts of the relay outputs required
Cable length between sensor and electronic
evaluation device with Cu 1.5 mm² and
150 nF/km maximum
3SK1 safety relays
Manual, 04/2013, A5E02526190021A/RS-AA/01
3SK1111-.AB..
A
5
A
0.2
A
0.1
A
4
A
4
A
1
A
0.2
A
0.1
A
1.5
A
1.5
A
5
A
12
10 000 000
V
gL/gG: 6A or circuit breaker type A: 3A or circuit
breaker type B: 2A or circuit breaker type C: 1A
m
2 000
Technical data
13.2 Basic units
3SK1111-.AW..
199