SIMATIC NET
S7-300 - Industrial Ethernet /
PROFINET
CP 343-1
Manual
Manual Part B
12/2018
C79000−G8976−C201-08
___________________
Preface
___________________
Properties / services
___________________
Performance data
___________________
Requirements for use
___________________
LEDs
Installation, connecting up
___________________
and commissioning
___________________
Configuration and operation
___________________
Service and maintenance
___________________
Technical specifications
___________________
Approvals
___________________
References
1
2
3
4
5
6
7
8
A
B

Advertisement

Table of Contents
loading

Summary of Contents for Siemens CP 343-1

  • Page 1 Properties / services ___________________ SIMATIC NET Performance data ___________________ Requirements for use S7-300 - Industrial Ethernet / PROFINET ___________________ LEDs CP 343-1 Installation, connecting up ___________________ and commissioning Manual ___________________ Configuration and operation ___________________ Service and maintenance ___________________ Technical specifications...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Preface

    Under the front panel: printed text with MAC addresses and firmware version ⑥ X = placeholder for hardware product version Figure 1 CP 343-1 Validity and product names This description contains information on the following product: ● CP 343−1 Article number 6GK7343-1EX30-0XE0 Hardware product version 7 Firmware version V3.0...
  • Page 4 ● If you replace a module, the MAC address of the predecessor is adopted when you load the configuration data; configured ISO transport connections remain operable. You should also refer to the information in the section Replacing a module (Page 59). CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 5 – Programmed connections and IP configuration – PROFINET IO Current manual release on the Internet You will also find the current version of this manual on the Internet pages of Siemens Automation Customer Support under the following entry ID: Link: (http://support.automation.siemens.com/WW/view/en/24485272) CP documentation in the Manual Collection (order no.
  • Page 6 You will find license conditions in the following document on the supplied data medium: ● OSS_CP3431_86.pdf Firmware The firmware is signed. This ensures that only firmware created by Siemens can be downloaded to the device. Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks.
  • Page 7 Siemens contact. Keep to the local regulations. You will find information on returning the product on the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/view/109479891) CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 8: Manual, 12/2018, C79000−G8976−C201

    Preface CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 9: Table Of Contents

    Influence of MPI on connections via Industrial Ethernet ............49 PROFINET IO ......................... 49 6.6.1 How PROFINET IO devices start up in a large configuration ..........49 6.6.2 PROFINET IO when operating other services at the same time ..........49 CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 10 Replacing older modules ....................... 60 7.4.2 Module replacement / upgrading ................... 60 7.4.3 Replacing a module without a programming device .............. 62 Technical specifications ........................65 Approvals ............................. 67 References ............................71 Index ..............................77 CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 11: Properties / Services

    Enhanced functions Abbreviations used with the CP 343-1 module The module abbreviations used below for the CP 343-1 (for example EX30) correspond to the last four characters of the mid section of the order number. Requirement for configuring new functions of firmware version V3.0 To use the features listed below, the following STEP 7 version is necessary: ●...
  • Page 12: Communication Services

    Enhanced functions of earlier firmware versions and predecessor modules You will find an overview of the earlier firmware versions and predecessor modules in the version history of the Industrial Ethernet CPs on the Internet pages of Siemens Automation Customer Support under the following entry ID: 56699406 (http://support.automation.siemens.com/WW/view/en/56699406)
  • Page 13 – FETCH/WRITE services (server; corresponding to S5 protocol) via ISO transport connections, ISOonTCP connections and TCP connections; The addressing mode can be configured for FETCH/WRITE access as S7 or S5 addressing mode. – LOCK/UNLOCK with FETCH/WRITE services; – Connection diagnostics from the user program CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 14: Other Services

    IP address, the subnet mask and the address of a gateway. As an alternative to STEP 7, you have the option of assigning the connection configuration via a block interface in the user program (FB55: IP_CONFIG). Configuration of S7 connections using FB55 is not possible. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 15: The Cp As Web Server

    Using the integrated update center of the diagnostics pages, you can download new firmware versions and language files for the diagnostics buffer message texts. For detailed information on Web diagnostics, refer to the general Part A of this manual, /1/ (Page 71). CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 16 ● Chrome (recommended version: as of 12.0) ● Opera (recommended version: as of 9.2) ● Firefox (recommended version: as of 4.0) You will find these Web browsers, information and any necessary addons on the Internet. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 17: Performance Data

    You can, for example, operate: ● 16 S7 connections, of which – 8 PUT jobs – 8 GET jobs ● 16 SEND/RECV connections, of which – 2 ISO-on-TCP connections – 8 TCP connections – 6 UDP connections CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 18: Characteristics Of S7 Communication

    16 S7 connections. The same applies to BSEND/BRECV and USEND/URECV jobs. LAN interface - data field length generated by CP per protocol data unit sending 240 bytes / PDU • • receiving 240 bytes / PDU • • CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 19: Characteristic Data Of The Send/Receive Interface

    (as of V4.0) and AG_RECV (as of V4.0) blocks of data with the following lengths: 1 to 8192 bytes for ISO transport, ISO-on- • TCP, TCP 1 to 2048 bytes for UDP • Restrictions for UDP CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 20: Profinet Io Characteristic Data

    Size of the input area over all PROFINET IO devices ***) 1024 bytes max. Size of the output area over all PROFINET IO devices 1024 bytes max. Size of the IO data area per submodule of a module in an IO device CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 21 • Size of the consistency area for a submodule 240 bytes Permitted number of CP 343-1 modules that can be used as PROFINET IO controllers within an S7-300 station Note: Regardless of the CP type (EX30, GX30, GX31 ...), only 1 CP may be a PROFINET IO controller.
  • Page 22 1 for the CP itself, 1 per Interface, 1 per port, 1 for each plugged- in module in HW Config or per slot used. Table 2- 8 Example of calculating the user data of the CP 343-1 as an IO device Bytes Explanation...
  • Page 23: Characteristic Data Of The Integrated Switch

    To do this, open the properties dialog of the relevant port and select the "disabled" setting under "Options > Transfer medium / duplex". The port is turned off completely when it is disabled. The corresponding LED on the device (for example X1P1) is then turned off. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 24 Performance data 2.6 Characteristic data of the integrated switch CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 25: Requirements For Use

    CPU 312 IFM 6ES7 312-5AC02-0AB0 6ES7 312-5AC82-0AB0 CPU 313 6ES7 313-1AD03-0AB0 CPU 313C 6ES7 313-5BE00-0AB0 6ES7 313-5BE01-0AB0 6ES7 313-5BF03-0AB0 CPU 313C-2 DP 6ES7 313-6CE00-0AB0 6ES7 313-6CE01-0AB0 6ES7 313-6CF03-0AB0 CPU 313C-2 PtP 6ES7 313-6BE00-0AB0 6ES7 313-6BE01-0AB0 6ES7 313-6BF03-0AB0 CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 26 CPU 317-2 PN/DP 6ES7 317-2EJ10-0AB0 6ES7 317-2EK13-0AB0 6ES7 317-2EK14-0AB0 CPU 317F-2 DP 6ES7 317-6FF00-0AB0 6ES7 317-6FF03-0AB0 CPU 317F-2 PN/DP 6ES7 317-2FJ10-0AB0 6ES7 317-2FK13-0AB0 6ES7 317-2FK14-0AB0 CPU 317T-2 DP 6ES7 317-6TJ10-0AB0 6ES7 317-6TK13-0AB0 CPU 318-2 DP 6ES7 318-2AJ00-0AB0 CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 27 NCU572.4 with PLC 314C-2 DP 6FC5 357-0BB24-0AA0 NCU573.4 with PLC 314C-2 DP 6FC5 357-0BB34-0AA0 NCU561.5 with PLC 317-2 DP 6FC5 356-0BB15-0AA0 NCU571.5 with PLC 317-2 DP 6FC5 357-0BB15-0AA0 6FC5 357-0BB25-0AA0 NCU573.5 with PLC 317-2 DP 6FC5 357-0BB35-0AA0 CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 28: Project Engineering

    Locating the support package You can install the support package from your local file system if it is already stored there or from the Internet pages of Siemens Automation Customer Support. ● STEP 7 V5.5 You will find the support package (HSP) on the Internet at the following address: 23183356 (http://support.automation.siemens.com/WW/view/en/23183356)
  • Page 29: Programming

    You will find information on the current block versions and the current blocks for download on the Internet under: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15342/dl) With older module types, this recommendation assumes that you are using the latest firmware for the particular module type. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 30 Requirements for use 3.3 Programming CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 31: Leds

    The display on the front panel consists of the following LEDs that indicate the operating mode and communications status. Figure 4-1 LEDs of the CP 343-1 The LEDs have the following meaning: ● SF: Group error ● BF: Bus fault on Ethernet interface ●...
  • Page 32 Firmware activation after loading using the Firmware Loader is active. * Firmware was successfully downloaded. * Firmware download aborted. * Module fault / system error Does not apply to loading via the update center in Web diagnostics. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 33 You click the "Flash" button in the update center. • In STEP 7 You click the "Flash" button in the "Browse network" dialog If you click the "Identify" or "Flash" buttons, all the port LEDs of the PROFINET interface flash briefly. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 34 LEDs CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 35: Installation, Connecting Up And Commissioning

    General notices on use in hazardous areas WARNING Risk of explosion when connecting or disconnecting the device EXPLOSION HAZARD DO NOT CONNECT OR DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 36 General notices on use in hazardous areas according to ATEX WARNING Requirements for the cabinet/enclosure To comply with EU Directive 94/9 (ATEX95), this enclosure must meet the requirements of at least IP54 in compliance with EN 60529. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 37: Installing The Cp, Connecting Power And Ground

    Pulling/plugging the CP when the power is on is not permitted. You should also remember that by removing a module from the rack, all modules on the other side of it will be disconnected from the CPU. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 38 ● Slider pushed in: Chassis ground and reference ground are connected (caution: you can feel the slider lock into position). ● Slider pulled out: There is no connection between chassis ground and reference ground. When shipped: Slider pushed in Use a screwdriver to set the slider. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 39 – To download the defined configuration The PG / PC requires a LAN attachment, for example via a CP 1613 or CP 1411 and must have the necessary software (for example the S71613 package or SOFTNET IE). The CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 40: Connecting The Cp To Ethernet

    Connecting the CP to Ethernet Connecting interface X1 to Industrial Ethernet 1. Connect the CP to Industrial Ethernet via one of the RJ45 jacks. 2. Where necessary, connect another component to the remaining free RJ45 jack. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 41 Connecting switches Note MRP configuration With an MRP configuration, keep to the setup guidelines for MRP. You will find examples of network attachments in the general Part A of this manual, see /1/ (Page 71). CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 42 Installation, connecting up and commissioning 5.3 Connecting the CP to Ethernet CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 43: Configuration And Operation

    ● Keep the firmware up to date. Check regularly for security updates of the firmware and use them. ● Check regularly for new features on the Siemens Internet pages. – Here you will find information on industrial security: Link: (http://www.siemens.com/industrialsecurity) –...
  • Page 44 Table: Meaning of the column titles and entries The following table provides you with an overview of the open ports on this device. ● Protocol / function Protocols that the device supports. ● Port number (protocol) Port number assigned to the protocol. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 45 Make sure that you enable the required client ports in the corresponding firewall on the communications partners and in intermediary routers. These can be: ● NTP / 123 (UDP) ● DNS / 53 (UDP) ● DHCP / 67, 68 (UDP) CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 46: Project Engineering

    ● Module access protection: Not locked The functions cannot be executed. ● Module access protection: Status-dependent With this setting, it is only possible to access the CP when the CPU is in STOP mode. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 47: Network Settings

    You will find information on the currently used network settings in STEP 7 as follows: ● In STEP 7 special diagnostics under the diagnostics object "Industrial Ethernet" in the "Network Connection" group box ● in STEP 7 with the menu command "PLC > Module Information" ● In Web diagnostics CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 48 Example: The download is started initially with the setting TP/ITP at 10 Mbps half duplex. If the "Individual network setting" is now changed to 100 Mbps full duplex, the download cannot be completed. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 49: Influence Of Mpi On Connections Via Industrial Ethernet

    (FB55, Primary Setup Tool, STEP 7, NCM Diagnostics): Note The functions listed above can influence the flow in PROFINET IO so that an interruption of cyclic IO data exchange of the PROFINET IO devices lasting several seconds may occur. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 50: Effects Of Multicast Communication On Rt Communication

    If a double IP address is detected, the CP also reports this via the LED (BF) and generates an entry in the diagnostics buffer. The CP remains in RUN mode. If the conflict is eliminated on another component, the "BF" LED goes off again. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 51: Obtain Ip Address Vie Dhcp: Cp Stop On Expiry Of The Lease

    You can use the CP in a ring topology with media redundancy. The CP can only be a redundancy client. For more detailed information on configuration, refer to the online help of the "Media redundancy" tab and Part A of the manual, see /1/ (Page 71). CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 52: Timeofday Synchronization

    For more detailed information on working with MIB files, refer to the documentation of the SNMP client you are using (example of an SNMP client: SNMP OPC server from SIMATIC NET). You will find more information on MIBs on the following SIMATIC NET Internet page: 15177711 (http://support.automation.siemens.com/WW/news/en/8797900) CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 53 This group returns status information about the CP interfaces. The MIB objects of the ifTable provide the status information of the interfaces. The "ifIndex" object identifier is assigned to the CP interfaces as follows: Table 6- 1 Assignment of ifIndex ifIndex Type of interface Port 1-2 Internal CP interface CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 54: Possible Security Gaps On Standard It Interfaces: Preventing Unauthorized Access

    If you have questions on the use of firewall systems and IT security, please contact your local Siemens office or representative. You will find the address in the SIMATIC catalog IK PI or on the Internet at the following address: (http://www.automation.siemens.com/partner/guisearch.asp)
  • Page 55: Programmed Communication Connections

    IPACL. Communication with unspecified nodes is only possible when IP access protection is enabled if the IP addresses were entered previously in the ACL during configuration. How to configure IP access protection is described in the general part of this manual /1/ (Page 71). CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 56: Permitted Length Of Icmp Packets

    40 s before the connection abort is recognized in the block. Block processing is aborted and the block resource is available again. This applies to BSEND (FB12), BRCV (FB13), USEND (FB8), URCV (FB9). With PUT/GET, block processing cannot be aborted. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 57: Service And Maintenance

    – In STEP 7 V5.5 with the menu command "PLC" > "Clear/Reset" – In STEP 7 special diagnostics with the "Operating Mode" > "Clear/Reset Module" menu command – In STEP 7 Professional V11 with STEP 7 special diagnostics CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 58: Memory Reset - Acl

    – The S7ONLINE interface must be set to the "ISO - Industrial Ethernet" protocol. It is not possible to download using TCP/IP (and therefore not to other networks). Always run the download using the active MAC address of the CP! CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 59: Replacing A Module

    If the CP has been used previously in your plant or has been repaired, delete all stored data by resetting to the factory settings. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 60: Replacing Older Modules

    7.4.2 Module replacement / upgrading Replacing a module The CP 343-1 (6GK7 343-1EX30-0XE0) described here can be used as a replacement for the following predecessor products: ● CP 343-1 (6GK7 343-1EX10-0XE0) ● CP 343-1 (6GK7 343-1EX11-0XE0) ●...
  • Page 61 Service and maintenance 7.4 Replacing a module The CP 343-1 (EX30) can be used along with a dummy module SM370 (6ES7 370-0AA01-0AA0) in any double width slot of an existing S7-300 rack. The SM370 dummy module has a switch on the rear that you need to set to the position "NA" in this case.
  • Page 62: Replacing A Module Without A Programming Device

    The configuration data of the CP is stored optionally on the CPU or CP. Replacing the CP with a module of the same type (identical order number) without a PG is only possible if the data is stored on the CPU. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 63 If, in exceptional situations, you have configured a new MAC address instead of the MAC address set in the factory, the configured MAC address will always be transferred to the DHCP server and the CP also receives the same IP address as the replaced module. CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 64 Service and maintenance 7.4 Replacing a module CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 65: Technical Specifications

    Dimensions (W x H x D) 40 x 125 x 120 mm Installation options Mounting in an S7-300 rack Product functions * * You will find the product functions in the section Properties / services (Page 11). CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 66 Data" see /12/ (Page 74) in the section "General Technical Specifications" on the topics listed below applies to the CP: ● Electromagnetic compatibility ● Transportation/storage conditions ● Mechanical and climatic environmental conditions ● Information on insulation checks, protection class and degree of protection CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 67: Approvals

    Approvals for shipbuilding are not printed on the device type plate. Current approvals on the Internet You will find the current approvals for the product on the Internet pages of Siemens Industry Online Support. Link: (http://support.automation.siemens.com/WW/view/en/10806075)
  • Page 68 Important notes on using the device (Page 35). You should also note the information in the document "Use of subassemblies/modules in a Zone 2 Hazardous Area" that you will find on the Internet at the following address: Link: (https://support.industry.siemens.com/cs/ww/en/view/78381013) CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 69 Zone 2 Hazardous Area" that you will find here: ● In the SIMATIC NET Manual Collection under "All documents" >"Use of subassemblies/modules in a Zone 2 Hazardous Area" ● On the Internet at the following address: Link: (https://support.industry.siemens.com/cs/ww/en/view/78381013) CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 70 Class I, Division 2, Group A, B, C, D, Temperature Class T4A; Ta = 0 °C...60 °C Class I, Zone 2, Group IIC, Temperature Class T4; Ta = 0 °C...60 °C Notice for Australia (C-TICK) AS/NZS 2064 (Class A) Notice for Korea (KCC) KCC-REM-S49-S7300CP CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 71: References

    References Finding the SIMATIC NET documentation ● Catalogs You will find the order numbers for the Siemens products of relevance here in the following catalogs: – SIMATIC NET Industrial Communication / Industrial Identification, catalog IK PI – SIMATIC Products for Totally Integrated Automation and Micro Automation, catalog...
  • Page 72 Part of the documentation package "STEP 7 Basic Knowledge" (Part of the online documentation in STEP 7) On programming SIMATIC NET Program blocks for SIMATIC NET S7 CPs Version history, reference document Siemens AG Entry ID: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15342/dl) CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 73 Link: (https://support.industry.siemens.com/cs/ww/en/view/62543517) /11/ Automatisieren mit STEP 7 in AWL und SCL (ISBN: 978-3-89578-280-0) / Automating with STEP 7 in STL and SCL (ISBN: 978-3-89578-295-4) User manual, programming manual Berger, Hans Publicis KommunikationsAgentur GmbH, GWA, 2006 CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 74 PROFINET System Description System manual Siemens AG (SIMATIC NET Manual Collection) On the Internet under following entry ID: 19292127 (http://support.automation.siemens.com/WW/view/en/19292127) /14/ SIMATIC From PROFIBUS DP to PROFINET IO Programming manual Siemens AG (SIMATIC NET Manual Collection) CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 75 ● Configuring Hardware and Connections with STEP 7 (ID: 18652631) ● From S5 to S7, Converter Manual (ID: 1118413) Siemens AG Order number 6ES7 810-4CA08-8AW0 (part of the online documentation in STEP 7) Other topics /19/ Ethernet, IEEE 802.3 (ISO 8802-3) http://www.ieee.org (http://www.ieee.org) CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 76 References B.8 Other topics /20/ RFC 1006 (ISO Transport Service on top of the TCP Version: 3) Request For Comment http://www.ietf.org (http://www.ietf.org) /21/ RFC 793 (TCP) http://www.ietf.org (http://www.ietf.org) /22/ RFC 791 (IP) http://www.ietf.org (http://www.ietf.org) CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...
  • Page 77: Index

    Access coordination, 5 SIMATIC NET Manual Collection, 5 STEP 7, 4 STEP 7 version, 11, 28 Glossary, 6 GSDML file, 29 Version history, 5 Hazardous area, 35 Hazardous areas according to ATEX, 36 IP configuration, 5 CP 343-1 Manual, 12/2018, C79000−G8976−C201-08...