6 Application Notes
Precautions for High Frequency/Low Impedance Motors
High frequency motors exhibit different characteristics than standard 60/120 Hz maximum
frequency motors. The low impedance associated with these high frequency motors often
requires manually programming a custom V/f pattern into the E1 parameter group to obtain
proper performance and rated power from the drive-motor combination.
The low impedance may also cause excessive motor current. In addition to considering the
use of an output reactor, it may be advantageous to oversize the drive to accommodate the
high peak current that may result from the low impedance motor. Using a drive that is at
least one or two models larger than the motor FLA may also help eliminate the oL2 faults.
Compatibility between the drive, motor, and the reactor is best accomplished via testing and
observation of the motor current waveform with an oscilloscope.
Reactor on page
16.
Revision History
The revision dates and the numbers of the revised manuals appear on the bottom of the back
cover.
MANUAL NO. TM.V1000SW.134A
Published in U.S.A.
Revision No.
Publication Date
First Version
18
Software No.
2009.11.06
VSV910050
YASKAWA ELECTRIC TM.V1000SW.134A 1000 Hz High Frequency Custom Software Supplement
November 2009 09-11
Date of
publication
Refer to Using an Output
1
Revision number
Date of original
publication
Revised Content
-

Advertisement

loading

This manual is also suitable for:

Vu*b****ba*-134 seriesVu*b****fa*-134 series