Administrator Settings; V.7.A. Configuration Menu With Admin Level Access; V.7. Administrator Settings - Caladair Freetime Series Operating And Commissioning Instructions

High efficiency recovery unit
Table of Contents

Advertisement

OPERATING AND COMMISSIONING INSTRUCTIONS

V.7. Administrator settings

Activation of the communication, dehumidification and fire function requires an access to Configuration menu in system
level. You have to get the access rights to « Admin » level. Follow the instructions below:
Access rights
Enter 1111 with directionnal arrows and validate with OK button. Press left arrow twice to reach the menu. In case of mistake
press C button twice and start again

V.7.a. Configuration menu with admin level access

Configuration
1 et 2 Activation MODBUS RS485 and settings (see chapter V.8)
3 et 4 Activation BACNET MSTP and settings (see chapter V.8)
5 et 6 Settings TCP/IP(see chapter V.8)
7 et 8 Activation du BACNET IP and settings (see chapter V.8)
9 Adressage Repetiteur (voir chapitre V.8)
MS-CDF-010
Enter
Communication
Système
Ind F
Maj. 18/05/2017
® -
FREETIME
HEXAMOTION
High Efficiency Recovery Unit
Enter password 1111
Of the required autoris.
Current level : ADMIN
Port 1
Communication
Esclave
Modbus esclave
Port 1
Active (1)
Communication
Bacnet
Port 1
Active (3)
TCP/IP
DHCP : OUI (5)
Ip actuel
Communication
Bacnet IP
Active (7)
Adresses
PLA : 254 (9)
ELA : 254 (9)
Créé par : JC
®
Adresse Modbus : 1 (2)
Vitesse : 9600 Bps (2)
2 bits d'arrêt : Oui (2)
Parité Non (2)
Device name : - (4)
MSTP
Mac : 0 (4)
Id appareil Bas : 2640 (4)
Id appareil Haut : 0 (4)
(x10000)
Vitesse : 9600 Bps(4)
Ad. maître max : 127 (4)
IP : - (6)
Subnet Mask - (6)
:
Subnet Mask - (6)
Gateway
- (6)
Device name : - (8)
Adresse BBMD : 0 (8)
Id appareil Bas : 2640 (8)
Id appareil Haut : 0 (8)
(x10000)
N° port UDP bas 7808(8)
N° port UDP haut 4(8)
(x10000)
Validé par : AR
Page 36/57

Advertisement

Table of Contents
loading

Table of Contents