OPERATING AND COMMISSIONING INSTRUCTIONS

V.4.c. Temperature setpoint modification

[(8) chapter V.3.b]
Access : temperature Regul
Regulation is based on the temperature control of :
Supply with external compensation (set in standard). Supply temperature setpoint follows outside temperature in
o
compliance with RT 2012 norm.
Extracxt
o

V.4.d. Forced stop of the unit or forced start LS or HS on the remote control

[(7) chapter V.3.a]
Access : running Mode / running Mode
You can stop (7) (stop) unit with CORRIGO controller or do a forced start LS (7) (manual speed 1/2) or HS (7) (manual
speed 1/1). In standard unit works automatically with clocks (7) (Auto)
If unit do not work in automatic mode an alarm will start. Manual speed 1/1 and manual speed 1/2 modes must be used
only for the commissioning and repair. An other setting will lead to a failure of the unit.

V.4.e. Choice of language

[(10) chapter V.3]
Access: Starting screen / language choice
V.5. Intermediate settings (service level)
Type of regulation type setting, Night Cooling parameters and CO2 setpoint require an acess to the Configuration menu.
You need the access right to the « Service » level. Follow the instrcuctions below.
Access right
Enter 2222 with directional arrows and validate with OK. Press left arrow twice to reach the access of the menus. In case of
mistake press C button twice and start again.
MS-CDF-010
Enter
Ind F
Maj. 18/05/2017
® -
FREETIME
HEXAMOTION
High Efficiency Recovery Unit
Enter password 2222 of the
required level :
Current level : SERVICE
Créé par : JC
®
Validé par : AR
Page 34/57