Iv.16. Dehumidification Function - Caladair Freetime Series Operating And Commissioning Instructions

High efficiency recovery unit
Table of Contents

Advertisement

OPERATING AND COMMISSIONING INSTRUCTIONS
2.
«continuous work » : Start of the unit in HS, fire function will have priority on all the other alarms.
3.
«Normal work» : keeps the unit running with parameters activated on site (Stop/LS/HS)
4.
« Supply fan only » : start or keeps in HS the supply fan (extract stopped)
5.
« Extract fan only » : starts or keeps in HS the extract fan (supply stopped)
Digital input « external stop » is priority on fire function.
This function is not adapted anymore to the French market and will be in all cases validated by the control office.
Digital input fire alarm will be connected between DI8 terminal of the controller and 13 of the terminal block (free voltage
contact required)
)
IV.16.
Dehumidification function
See parameters in chapiter V.8
It is possible to associate the unit to a COMBIBOX CONCEPT
expansion module only) followed by a hot battery (water or electric or hot direct expansion module DX heat). In this case
controller will manage automatically the heating or cold inputs for the dehumidification and will keep an ideal functioning
temperature. During cold needs period, the temperature management will have priority on dehumidification.
Function non available in DIVA mode
Connect batteries as indicated in chapters IV.12, IV.14
Install the humidity duct sensor in supply or extract air, following the humidity control mode.
Connect the humidity sensor as following instructions :
MS-CDF-010
Ind F
Maj. 18/05/2017
® -
FREETIME
HEXAMOTION
High Efficiency Recovery Unit
®
module equipped with a cold battery (water or cold direct
Créé par : JC
®
Validé par : AR
Page 26/57