General Fonctionning; Iii.1. General; Iii.1.A. Freetime; Iii.1.A. Hexamotion - Caladair Freetime Series Operating And Commissioning Instructions

High efficiency recovery unit
Table of Contents

Advertisement

OPERATING AND COMMISSIONING INSTRUCTIONS
III. GENERAL FONCTIONNING

III.1. GENERAL

®
FREETIME
and HEXAMOTION
recovery meant for office and industrial installations. Its performance is greater than 80%.
FREETIME
III.1.a.
®
FREETIME
SEASON : Manages the fans by potentiometers and rotative exchanger. No battery can be associated.
®
FREETIME
FIRST : Econological management of fans and rotative exchanger. Allows managing a non-integrated
changeover battery or (hot water battery non-integrated or and cold water battery non integrated).
®
FREETIME
PREMIUM BC : Econological management of the fans, rotative exchanger and a hot water integrated battery.
If required, it can also manage a non-integrated cold water battery.
®
FREETIME
PREMIUM BE : Econological management of the fans, rotative exchanger and an electrical integrated battery.
If required, it can also manage a non-integrated cold water battery.

III.1.a. HEXAMOTION

®
HEXAMOTION
SEASON : Manages the fans by potentiometers and rotative exchanger. No battery can be associated.
®
HEXAMOTION
FIRST : Econological management of fans and rotative exchanger. Allows managing a non-integrated
changeover battery or (hot water battery non-integrated or and cold water battery non integrated).
®
HEXAMOTION
PREMIUM CO : Econological management of the fans, rotative exchanger and a changeover water
integrated battery. If required, it can also manage a non-integrated cold water battery.
®
HEXAMOTION
PREMIUM BE : Econological management of the fans, rotative exchanger and an electrical integrated
battery. If required, it can also manage a non-integrated cold water battery.
®
HEXAMOTION
PREMIUM DXR : Econological management of the fans, rotative exchanger and an reversible directe
expension battery.

III.2. FUNCTIONNAL ANALYSIS

Except SEASON version
Starting sequence :
The supply air fan starts and the fresh air register opens.
o
o
The extract air fan starts and the extract air register opens
Temperature regulation starts defined in the regulation mode set. Electric heater (if set), starts with airflow controller.
o
Pumps start.
After a defined time, alarms management function is activated. Installation is in normal mode.
o
Start conditions :
Installation starts when one of these conditions are filled:
Timer normal or reduced are activate
o
Manual start is activated with controller
o
One of the digital input for extended operation is activated.
o
Stop sequence :
Installation stops with following process:
o
Deactivation of the alarm management function.
Electric heater stops (if set).
o
After a defined time (individually defined for each fan) fans are stopped.
o
Supply and return air registers are closed .
o
Signals toward actuator are reset and pumps closed
o
Stop conditions :
Installation stops when one these conditions are filled:
Timers normal or reduced are not activated and digital input for extended operation is not activated.
o
Digital Input for External stop is activated.
o
Manual stop is activated with controller
o
An alarm configured with stop function is activated. Installation will automatically start when alarm is reset.
o
MS-CDF-010
®
range are programme of double-flow units with high efficiency recovery, self-regulating
®
®
Ind F
Maj. 18/05/2017
® -
FREETIME
HEXAMOTION
High Efficiency Recovery Unit
Créé par : JC
®
Validé par : AR
Page 9/57