V.5. Administrator settings

Activation of the communication, dehumidification and fire function requires an access to Configuration menu in system
level. You have to get the access rights to « Admin » level. Follow the instructions below:
Access rights
Enter 1111 with directionnal arrows and validate with OK button. Press left arrow twice to reach the menu. In case of mistake
press C button twice and start again

V.5.a. Configuration menu with admin level access

Configuration
1 et 2 Activation MODBUS RS485 and settings (see chapter V.6)
3 et 4 Activation BACNET MSTP and settings (see chapter V.6)
5 et 6 Settings TCP/IP(see chapter V.6)
7 et 8 Activation du BACNET IP and settings (see chapter V.6)
9 Adressage Repetiteur (voir chapitre V.6)
MS-CDF-002
Enter
Quitter
Communication
Système
Ind D
Maj. 02/11/2018
EXAECO
HIGH EFFICIENCY RECOVERY UNIT
Enter password 1111
Of the required autoris.
Current level : ADMIN
Port 1
Communication
Esclave
Modbus esclave
Port 1
Active (1)
Communication
Bacnet
Port 1
Active (3)
TCP/IP
DHCP : OUI (5)
Ip actuel
Communication
Bacnet IP
Active (7)
Adresses
PLA : 254 (9)
ELA : 254 (9)
Créé par : JC
®
Adresse Modbus : 1 (2)
Vitesse : 9600 Bps (2)
2 bits d'arrêt : Oui (2)
Parité Non (2)
Device name : - (4)
MSTP
Mac : 0 (4)
Id appareil Bas : 2640 (4)
Id appareil Haut : 0 (4)
(x10000)
Vitesse : 9600 Bps(4)
Ad. maître max : 127 (4)
IP : - (6)
Subnet Mask - (6)
:
Subnet Mask - (6)
Gateway
- (6)
Device name : - (8)
Adresse BBMD : 0 (8)
Id appareil Bas : 2640 (8)
Id appareil Haut : 0 (8)
(x10000)
N° port UDP bas 7808(8)
N° port UDP haut 4(8)
(x10000)
Validé par : AR
Page 30/49