OPERATING AND COMMISSIONING INSTRUCTIONS

III.3. MODE DE REGULATION

III.3.a. SEASON :

1 Adjustable speeds from potentiometers
Each fan is individually adjustable from integrated potentiometer
Possibility to add a remote forced stop (in standard on supply contactor (not supplied))

III.3.b. ECO :

1 or 2 speeds adjustable « MODE VENTIL (%) »
Adjustment of a minimum speed (LS - 1/2) and a maximum speed (HS - 1/1) in %.
Fitted with a factory turned clocked set :
(HS - 1/1) from 06h00 to 22h00
o
(LS - 1/2) from 22h00 to 06h00
o
Possibility of adding a remote forced start (LS - 1/2) or (HS - 1/1) (free voltage contact NO)
Possibility of adding a remote forced stop (free voltage contact NO)

III.3.c. DIVA

Proportional ventilation between two airflows (LS/HS) with CO2 management
« AUTO CO2 MODE »
Adjustment of a minimum speed (LS - 1/2) and a maximum speed (HS - 1/1) in %.
CO2's setpoint is set in factory to 1000ppm (compliant to French RT2012).
Variation between (LS - 1/2) and (HS - 1/1) is managed from CO2 level
Fitted with a factory turned clocked set in (LS - 1/2) from 00h00 to 24h00.
Possibility of adding a remote forced start (LS - 1/2) or (HS - 1/1) (free voltage contact NO)
Possibility of adding a remote forced stop (free voltage contact NO)
Nota : In order for the CO2 regulation works, installation must follow these constraints :
Clock (HS - 1/1) is not activated (normal speed timer)
o
Clock (LS - 1/2) is activated (reduced speed Timer)
o
External operation (HS - 1/1) and external stop are not activated.
o

III.3.d. LOBBY

Constant pressure ventilation. (Pa) « CONSTANT PA MODE»
Constant pressure adjustement (Pa).
Fitted with a factory turned clocked set in (LS - 1/2) from 00h00 to 24h00.
Possibility of adding a remote forced start (LS - 1/2) (free voltage contact NO)
Possibility of adding a remote forced stop (free voltage contact NO)
III.3.e. MAC2
1 or 2 constant air flow (m
Adjustment of a minimum constant air flow (LS - 1/2) and a maximum air flow (HS - 1/1) in m3/h.
Fitted with a factory turned clocked set :
(HS - 1/1) from 06h00 to 22h00
o
(LS - 1/2) from 22h00 to 06h00
o
Possibility of adding a remote forced start (LS - 1/2) or (HS - 1/1) (free voltage contact NO)
Possibility of adding a remote forced stop (free voltage contact NO)
III.3.f. QUATTRO
Proportional ventilation between two constant airflows (m
Adjustment of a minimum constant air flow (LS - 1/2) and a maximum air flow (HS - 1/1) in m3/h.
CO2's setpoint is set in factory to 1000ppm (compliant to French RT2012).
Variation between (LS - 1/2) and (HS - 1/1) is managed from CO2 level
Fitted with a factory turned clocked set in (LS - 1/2) from 00h00 to 24h00.
Possibility of adding a remote forced start (LS - 1/2) or (HS - 1/1) (free voltage contact NO)
Possibility of adding a remote forced stop (free voltage contact NO)
Nota : In order for the CO2 regulation works, installation must follow these constraints :
MS-CDF-010
®
:
®
: (impossible with version FREETIME 500-800 et HEXAMOTION 05-08)
3
/h) adjustable « MODE CONSTANT M3/H »
®
: (impossible with version FREETIME 500-800 et HEXAMOTION 05-08)
Ind F
Maj. 18/05/2017
® -
FREETIME
HEXAMOTION
High Efficiency Recovery Unit
.
3
/h) adjustable with CO2 management
Créé par : JC
®
Vitesse GV
Vitesse PV
Vitesse GV
Vitesse PV
Validé par : AR
Page 10/57