Iv.3. Temperature Sensor Wiring (Except Season); (Except Season) - Caladair Freetime Series Operating And Commissioning Instructions

High efficiency recovery unit
Table of Contents

Advertisement

OPERATING AND COMMISSIONING INSTRUCTIONS
IV.3.
TEMPERATURE SENSOR WIRING (Except SEASON)
Temperature sensors are connected on the controller
SSG : Supply temperature sensor on Agnd(30) and AI1(31)
o
SEG : Outdoor temperature sensor on Agnd(30) et AI2(32)
o
o
SRG : Extract temperature sensor on Agnd(33) et AI3 (34)
IV.4.
TERMINAL BLOCKS OF FREETIME
Désignation
Bornes
ADP (shunted if not
1-2
used)
3-4
DAD (shunted if
not used)
5-6
THA/THS (shunted
if not used)
ED-TOUCH
7-8 + A*-B*
MF PV
9-10
11-12
MF GV
13-14
ARR EXT
MS-CDF-010
Raccordement
Connect on fire emergency stop (free voltage NC contact)
Connect on DAD (smoke detector) default contact (NC)
Connect to NC free voltage contact of THA (
Or
Connect to NC free voltage contact of THS (
Connect to remote touch screen display
(port2)
Connect to NO free voltage contact of reduced Speed extended operation
Connect to NO free voltage contact of normal Speed extended operation
Connect to NO free voltage contact of external stop
Ind F
Maj. 18/05/2017
® -
FREETIME
HEXAMOTION
High Efficiency Recovery Unit
®

(Except SEASON)

Créé par : JC
®
)
PREMIUM BC - CO
)
PREMIUM BE
Validé par : AR
Page 18/57