Technical specifications
A.2 Fail-Safe CPU technical specifications
A.2.3.5

CPU 1215FC wiring diagrams

Table A- 41
CPU 1215FC DC/DC/Relay (6ES7 215-1HF40-0XB0)
Table A- 42
168
Connector pin locations for CPU 1215FC DC/DC/Relay (6ES7 215-1HF40-0XB0)
Pin
1
L+ / 24VDC
2
M / 24VDC
3
Functional Earth
4
L+ / 24VDC Sensor Out
5
M / 24VDC Sensor Out
6
1M
7
DI a.0
8
DI a.1
9
DI a.2
10
DI a.3
11
DI a.4
12
DI a.5
13
DI a.6
14
DI a.7
X10
X11 (gold)
2M
AQ 0
AQ 1
3M
AI 0
AI 1
--
--
--
--
--
--
--
--
The two rectangular areas are
yellow. These are only on the
fail-safe CPUs.
24 VDC Sensor Power Out
For additional noise immunity,
connect "M" to chassis ground
even if not using sensor supply.
For sinking inputs, connect "-" to
"M" (shown).
For sourcing inputs, connect "+"
to "M".
Note: X11 connectors must be gold.
See Appendix B, Spare Parts for
article number.
X12
1L
DQ a.0
DQ a.1
DQ a.2
DQ a.3
DQ a.4
2L
DQ a.5
DQ a.6
DQ a.7
DQ b.0
DQ b.1
--
--
S7-1200 Functional Safety Manual