Fault Types, Causes, And Corrective Measures - Siemens SIMATIC S7 Functional Safety Manual

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

6.2.2

Fault types, causes, and corrective measures

The "Fault types, causes, and corrective measures" table below lists the messages of the
S7-1200 fail-safe SMs. These messages are displayed in the TIA Portal under "Online &
diagnostics" > "Diagnostics" > "Diagnostic buffer". When you highlight an individual text line
in the diagnostic buffer, the Event ID for that text item is displayed, along with module
identity and location that generated the message. You may need to expand the window to
see all information.
Table 6- 6
Fault types, causes, and corrective measures
Event ID
Diagnostic mes-
sage
0x0001
Short-circuit
0x0005
Overtemperature
0x004D
PROFIsafe
communication
error (CRC)
S7-1200 Functional Safety Manual
Manual, 02/2015, A5E03470344-AA
Fail-safe signal
Description
module
SM 1226 F-DQ
A channel problem
4 x 24 VDC
has been detected
where either the P
terminal or M termi-
nal is at an unex-
pected potential.
All
Overtemperature
at microcomputer
Overtemperature
at I/O
All
Transmission error in
data message frame:
Data inconsistent
(CRC (cyclic redun-
dancy check) error)
Fail-Safe signal module (SM) diagnostics
Possible causes
Corrective measures
Short-circuit of the
Eliminate the short-circuit.
output
Short-circuit be-
Eliminate the short-circuit.
tween channels with
different signals
Output overload
Eliminate the overload.
"Maximum readback
Increase "Maximum read-
time switch on test"
back time switch on test" if
value is configured
permissible.
too small
Short-circuit of out-
Eliminate the short-circuit.
put to M
Defective output
Replace the fail-safe signal
driver
module (SM).
Shutdown due to
Check the ambient tem-
violation of high
perature. Once the fault
temperature limit
has been eliminated, the
value in the module
power must be switched off
case
and on.
Communication
interference be-
tween the fail-safe
CPU and the fail-
safe signal module
(SM) (for example,
due to electromag-
netic interference in
excess of limits or
sign-of-life monitor-
ing error)
6.2 Fault diagnostics
1
Check the communica-
tions connection.
Eliminate the interfer-
ence.
125