Sm 1226 F-Dq 4 X 24 Vdc; Properties; User Data Space; A.3.3.1 Properties - Siemens SIMATIC S7 Functional Safety Manual

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

A.3.3

SM 1226 F-DQ 4 x 24 VDC

A.3.3.1

Properties

Article number
6ES7 226-6DA32-0XB0
Properties
The SM 1226 F-DQ 4 x 24 VDC has the following features:
● Four outputs, P- and M-switching
● 2 A output current
● Rated load voltage 24 VDC
● Suitable for solenoid valves, DC contactors, and indicator LEDs
● Module fault display (DIAG; green and red LED)
● Status display for each output (green LED)
● Fault display for each output (red LED)
● Safety class SIL 3 attainable
● Assignable diagnostics
● Refer to "Fault diagnostics" (Page 119) for a description of LED and diagnostic message
functions.
A.3.3.2

User data space

The SM 1226 F-DQ 4 x 24 VDC user data space is 4 process value output bits followed by 4
quality bits.
This is the bit structure for an F-DQ DC module configured with input start address 8:
S7-1200 Functional Safety Manual
Manual, 02/2015, A5E03470344-AA
Terminal
F-DQ a.0
F-DQ a.1
F-DQ a.2
F-DQ a.3
A.3 Fail-Safe signal module (SM) technical specifications
Process value
Q8.0
Q8.1
Q8.2
Q8.3
Technical specifications
Quality bit
I8.0
I8.1
I8.2
I8.3