A-4
Configure Modules in RSLogix 5000 Software
Work with the
Fault/Program Action
Dialog
Publication 1734-UM003B-EN-P - August 2005
Use these procedures to complete the entries from this dialog, which
is not available with a Listen Only connection.
1. Check the checkboxes, as shown in the table.
Check this
To
Checkbox
Counter Reset
Reset the counter
Counter Preset
Set the value of the counter, as specified by the preset words
Value Reset
Reset the value of the accumulated (stored) count
2. If you selected PWM for Type, proceed as follows; otherwise,
see the next step.
a. For PWM Hold State, make a selection as follows.
- Check the checkbox to disable the PWM Value field.
- Uncheck the checkbox to set the PWM Value field.
b. For Value, select 0 -95%, if you did the following.
- Selected PWM for Type.
- Unchecked the checkbox for PWM Hold State.