Left Hand Position
Back Position
Machine room must be built in accordance with elevator manufacturer and applicable building codes and
o
regulations. Adequate ventilation is required to maintain a temperature of 50° to 120°F for output of 3600 BTU
per hour.
A convenience outlet of 115 VAC 15 Amp single-phase with G.F.I. shall be located next to the light switch in
o
the machine room (provided and installed by others).
Provide lockable, in open position, fused disconnect switches located adjacent to the elevator controller.
o
Fusing must be selectively coordinated. Fuse either 208V three-phase w/30 Amp or 240V single-phase w/40
Amp service; fuse 115V for 15 Amp service for cab lighting. (Must comply with applicable codes.)
The electrical circuit provided shall be either 30 Amp 208V three-phase or 40 Amp 240V single-phase,
o
dedicated circuit with equipment ground. The circuit shall terminate on the line side terminal lugs of the
disconnect. The electrical circuit is provided and installed by others.
o
Disconnect switch to have auxiliary normally open interlock switch. Interlock equal to Square D EK-300-Z.
30" wide x 36" deep work space required in front of the disconnects and the elevator controller.
o
Machine room lighting shall be a minimum of 19 foot-candles (204 lux) at working surfaces. The switch
o
for the light must be within 18" of the strike side of the machine room door. The light must be guarded to
prevent accidental breakage or contact with the hot bulb. The switch, light, wiring, and guard are provided
and installed by others.
A telephone line circuit is to be provided and installed by others. This circuit shall be brought to the machine
o
room controller in conduit. This circuit must be connected to a dedicated outside line or a 24 hour central
exchange.
The elevator controller/pump unit dimensions - 27.5" wide x 62.8" high x 16.15" deep with 39" clear space in
o
front.
Machine room access door must be self closing, self locking, key locked and have a spring return latch.
o
o
Consult local building codes for door construction. The door and hardware are both provided and installed by
others.
Machine room is required to be free of all pipes, wiring and obstructions not related to the operation of the
o
elevator. Provide a 4 inch conduit from the lift shaft to the remote machine room.
Part No. 000682 15-m10-2015

MACHINE ROOM OPTIONS

5 ft 0 in. min.
5 ft 0 in. min.
230/208 Disconnect
115 V Cab Lighting Disconnect
Machine Room Light Switch
GFI Duplex Wall Recetacle
Right Hand Position
Remote Position
Orion Planning Guide