Logical Functions - MDT AKS-0410.01 Manual

Standard / heavy c-loads / compact switch actuators
Hide thumbs Also See for AKS-0410.01:
Table of Contents

Advertisement

 Technical Manual Switch Actuators AKI/AKS/AKK
 
4.4.3 Logical functions
 
The following illustration shows the setting options at the ETS‐Software: 
Illustration 14: Logical functions 
 
The logic function can be activated with one or two objects. The objects are the inputs of the logic 
block. Furthermore you can choose between an AND‐function and an OR‐function. 
When you have activated the logic function, the logic block has to be satisfied before switching the 
channel. As long as the logic function is not satisfied, the channel does not react to any signal. 
 
The following chart shows the relevant communication objects: 
Number 
Name 
Logic 1 
Logic 2 
Chart 15: Communication objects logic 
 
According to the chosen logic operation only one or both objects have to become a 1‐signal. 
The following chart shows the both logic operations with two objects: 
AND‐Connection 
 
 
Chart 16: Logic operations 
 
 
 
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
20
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
Length
1 Bit 
1 Bit 
 
Logic 1 
Logic 2 
Channel 
switchable?
No 
No 
No 
Yes 
 
Usage
Logic object 1, is the first input for the logic 
block  
Logic object 2, is the second input for the logic 
block  
 
 
OR‐Connection 
 
Logic 1 
Logic 2 
Channel 
switchable?
No 
Yes 
Yes 
Yes 
 