4.5

Arrangement of modules on a single rack

Reasons for using one or multiple racks
The number of racks you need will depend on your application.
Reasons for using a single rack:
Note
If you opt for the installation on a single rack, insert a dummy module to the right of the CPU
(order no.: 6ES7 370-0AA01-0AA0). This gives you the option of adding a second rack for
your application, simply by replacing the dummy module with an interface module, and
without having to reinstall and rewire the first rack.
Rules: Layout of modules on a single module rack
The following rules apply to module installations on a single rack:
• No more than eight modules (SM, FM, CP) may be installed to the right of the CPU.
• The accumulated power consumption of modules mounted on a rack may not exceed
Reference
For further information, refer to the technical data, for example, in the
Specifications Reference Manual
Example
The figure below shows a layout with eight signal modules in an S7-300 assembly.
S7-300, CPU 31xC and CPU 31x: Installation
Operating Instructions, Edition 08/2004, A5E00105492-05
Compact, space-saving use of all your
modules
Local use of all modules
Fewer signals to be processed
1.2 A on the S7-300 backplane bus.
PS
CPU
4.5 Arrangement of modules on a single rack
Reasons for distributing modules between
several racks
Reference Manual
or in the
SM1 SM2 SM3 SM4 SM5 SM6 SM7 SM8
More signals to be processed
Insufficient number of slots
S7-300 Module
for your CPU
Configuring
.
4-7