Wait Function - Samwontech TEMP2020 series Operation Manual

Table of Contents

Advertisement

SAMWONTECH

5.5 WAIT function

▶ Press [WAIT SET] button on PROTRAM SET menu screen to enter into this screen.
▶ This screen is to set WAIT Function parameter.
▶ WAIT Function established on this screen can be applied to program segment setting on [5.1 Program
PATTERN].
▶ Following screen is explained for CH1, and CH2 uses the same screen as CH1.
※ Description of WAIT Function
­ Operating condition for WAIT Function
☞ When Process Value does not reach the Wait Operation Setting Zone within Segment Time setting.
­ Release condition for WAIT Function
☞ When the Process Value reaches to Wait Operation Setting Zone.
­ WAIT operation will be released and program operation will step to the next segment (N+1).
① Setup box to set whether or not using WAIT Function.
② Setup box to establish WAIT ZONE to release WAIT Operation.
③ Set Wait Time to apply when the Process Value does not reach Wait Zone.
☞ When 00.00 default value of WAIT TIME, WAIT operation will be pending infinitely until released.
④ Setup box for applicable range of WAIT Function.
☞ When "All" is selected, Wait is applied to all Segments setting in [5.1 PROGRAM PATTERN].
☞ When "Soak Seg" is selected, Wait is applied only to the soak segment setting in [5.1 PROGRAM
PATTERN].
⑤ Move to CH1 or CH2 screen.
Table 5-5. WAIT USE setting Parameters
Parameter
WAIT USE
CH1 WAIT ZONE
CH2 WAIT ZONE
WAIT TIME
WAIT USE METHOD
1st Edition of TEMP2020_Series IM : Dec. 15. 2008
[Figure 5-10] WAIT SET screen
Range
UNUSE, USE
CH1.EUS(0.00~100.00%)
CH2.EUS(0.00~100.00%)
00.00~99.59 (H,M)
ALL, SEG
Units
Default
ABS
UNUSE
CH1.EUS
CH1.EUS(0.00%)
CH2.EUS
CH2.EUS(0.00%)
ABS
00.00
ABS
Page 52 / 71
ALL

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Temp2520Temp2320Temp2720