Using ON/OFF Control

The procedure to use ON/OFF control is given step by step in this section.
Step 1 Determining the Control Method
Select direct or reverse operation.
1
The default setting is for reverse operation.
For heating control, select reverse operation.
Reverse Operation (Default)
ON
Heating
OFF
Set point
Output turns ON if the
temperature is lower than the
set point.
Adjust the hysteresis.
2
With ON/OFF control, you can adjust the reset width (called the hysteresis) for heating or cooling
operation. The default setting is 1.0°C.
Heating (Reverse) Operation
When the output turns OFF at the set point, the
temperature will decrease. You can set the
temperature width that determines when the
output will turn ON again.
ON
Heating
OFF
Set point
This width can be set as the
hysteresis.
Simplicity on the Worksite
Temperature
Output turns OFF if the
temperature is greater than
the set point.
Temperature
Solutions Guide for FAQs: E5CC/E5EC
Using ON/OFF Control
For cooling control, select direct operation.
Direct Operation (Default)
ON
Cooling
OFF
Set point
Output turns OFF if the
Output turns ON if the
temperature is lower than the
temperature is greater than
set point.
the set point.
Cooling (Direct) Operation
When the output turns OFF at the set point, the
temperature will increase. You can set the
temperature width that determines when the
output will turn ON again.
ON
OFF
Set point
This width can be set as the
hysteresis.
Temperature
Cooling
Temperature
2-1