Download Print this page

Omron E5CC Solution Manual page 14

Digital temperature controllers. using basic functions
Hide thumbs Also See for E5CC:

Advertisement

Using PID Control
Reference Information: PID Control
Problems with 100% Autotuning (AT-2)
If autotuning at 100% (AT-2) does not produce the desired results, you can also execute autotuning at
40% (AT-1).
●Autotuning at 40% (AT-1)
A 40% variation in the manipulated variable of the limit cycle is used for autotuning. Executing 40%
autotuning may require more time than executing 100% autotuning (AT-2).
The limit cycle timing varies according to whether the deviation (DV) at the start of autotuning execution is
less than 10% FS.
Deviation ≥ 10% FS
PV
SP
Deviation: 10% FS
AT started.
Simplicity on the Worksite
3-6
Limit Cycle MV
Amplitude: 40%
Time
AT ended.
Deviation < 10% FS
PV
Limit Cycle MV
Amplitude: 40%
SP
Deviation: 10% FS
AT started.
Solutions Guide for FAQs: E5CC/E5EC
Time
AT ended.

Hide quick links:

Advertisement

loading

This manual is also suitable for:

E5ec