Mj-4A & Mj-4B Control Panel Basic Troubleshooting; Introduction; Visual Inspection - Siemens MJ-4A Installation And Operation Manual

Voltage regulator control panel
Hide thumbs Also See for MJ-4A:
Table of Contents

Advertisement

8
8 MJ-4A & MJ-4B Control Panel Basic Troubleshooting
8.1

Introduction

MJ-4 Control Panel service is primarily accomplished at
the factory. However, certain basic procedures can be
accomplished in the field. This chapter outlines a set of
procedures whose major objectives are to:
1.
Ensure that the fault is inside the MJ-4 (and not in
external connections or connected equipment).
2.
Ensure that the fault is not due to improper jumper
arrangements or some other user-correctable condi-
tion.
3.
Determine whether the fault can be locally repaired
(e.g., by replacing a fuse).
Troubleshooting approaches depend upon the problem.
Among other indicators, you should consider:
Visual review of the unit.
Alerts (see Table 8.1 below).
8.2

Visual Inspection

Check:
Alert Messages
Table 8.1
Alert Name
Low Current
Check E1 and C2 wiring. Check calibration on the Current inputs.
Auto Inhibit
This alert does not indicate a fault condition. It indicates that Automatic Inhibit has been activated (either via the
communications link or via the Automatic Inhibit Input terminals
Tap Track Error
May indicate a temporary fault condition (failure to detect a transition on one of several input lines.) Check PDS sig-
nals J, K, U10 and U12.
Neutral Sig. Err
May indicate a temporary fault condition (failure to detect a transition on one of several input lines.) This alert could
also indicate a problem with the Neutralite
Tap Pos ????
May indicate a temporary fault condition (failure to detect a transition within the allowed time period on one of sev-
eral input lines.) Check the Neutral (PDS-U12) and Operations Counter (PDS-U10) inputs.
Low PT Thresh
This alert does not necessarily indicate an MJ-4 fault condition. Check to see whether this alert condition goes
away when both U2 and P2 are above the PT Threshold.
Overcurrent
This alert does not (normally) indicate an MJ-4 fault condition. Ensure that this Alert goes away when an in-range
current (0-200 mA) is applied at C2/E1.
NV RAM Reset
May indicate a temporary fault condition. If condition appears repeatedly, replace the unit.
Low Battery
Indicates that it is time to replace the Lithium Battery. If condition persists after a good battery is installed, check
that the battery was installed properly. If fault persists, consult the factory.
High Voltage
May indicate a temporary system fault condition. If condition persists when in-range voltages (90-140 VAC) are
applied to both PDS-U2 and PDS-P2 inputs, perform calibration.
Not in Auto
Indicates that Remote-Auto/Off/Manual switch is in Manual.
R Limit Reached,
These alerts indicate that the tap position has reached or exceeded the pre-set threshold. These alerts may occur
L Limit Reached
during normal operation due to system conditions. If these alerts occur when system conditions do not warrant it,
their occurrence could indicate an MJ-4 failure. Verify the MJ-4 can automatically raise and lower tap position.
Self Test Fault
This alert indicates a failure of one or more MJ-4 self tests. Consult your Siemens representative for instructions.
Siemens Energy, Inc.
MJ-4A & MJ-4B Control Panel Basic Troubleshooting
Power and Sensing fuses
External Source fuse (if External Source Terminals are
used to power the unit)
Fuse connectors not mated properly
Jumpers not in their correct positions
Terminal Strip connectors not mated properly
Terminal Strip connector jumpers missing or screws
not tightened properly
120 volts on terminal block, leads,
and inside control panel housing.
May result in minor or moderate injury
including equipment damage.
Disconnect all power sources before
making connections to the terminal block
or opening the control panel housing.
What to Check
input signal. Check the Neutral (PDS-U12) input.
CAUTION
55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mj-4b

Table of Contents